2003-01-09 00:00:00 | BUILDING REVIEW PROVISO: |
| 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS UNDER A SEPARATE PERMIT. |
| 2-FLOD ZONE A9: NEED TO PROVIDE THE |
| ELEVATION CERTIFICATE. |
| 3-SHEET A-1: REVISE/CLARIFY NOTE #24. |
| SEE SEC. 1007.5.1 FBC 2001 FOR HEIGHT |
| OF HANDRAILS.**NOTE: HANDRAILS AND |
| GUARDRAILS ARE NOT THE SAME. |
| 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE |
| THICKNESS IS LESS THAN 0.25". SECTION |
| 2405.2.2 FBC 2001. |
| 5-SHEET A-4: REVISE/CLARIFY NOTE #1. SEE |
| SEC. 1007.5.1 FBC 2001 FOR HEIGHT OF |
| HANDRAILS. **NOTE: HANDRAILS AND |
| GUARDRAILS ARE NOT THE SAME. |
| 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| AT ALL CONCEALED SPACES AS REQUIRED BY |
| SEC. 2305.1.4 FBC 2001. |
| 7-PROVIDE COMPLETE DETAIL/SECTION FOR |
| CONNECTION AT TOP OF COLUMN LOCATED |
| BETWEEN GARAGE AND KITCHEN. CLARIFY |
| HOW IS SPECIFIED STRAP HOLDING THE |
| TWO GIRDER TRUSSES. SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL |
| WALL SECTIONS FOR FIRECUT REQUIREMENTS |
| SEC. 2305.4 FBC 2001. |
| 9-DETAIL R19: CLEARLY SPECIFY ALL CONNEC |
| TORS. ROOF FRAMING PLAN DOESN'T SHOW |
| THEM.SEC. 104.2.1.2 CITY AMENDMENTS. |
| 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER |
| FOR GARAGE DOOR STRUCTURAL BUCK DETAIL |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |