Plan Review Notes
Plan Review Notes For Permit 02120174
Permit Number 02120174
Review Stop R
Sequence Number 1
Notes
Date Text
2003-01-09 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOD ZONE A9: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-SHEET A-1: REVISE/CLARIFY NOTE #24.
 SEE SEC. 1007.5.1 FBC 2001 FOR HEIGHT
 OF HANDRAILS.**NOTE: HANDRAILS AND
 GUARDRAILS ARE NOT THE SAME.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE/CLARIFY NOTE #1. SEE
 SEC. 1007.5.1 FBC 2001 FOR HEIGHT OF
 HANDRAILS. **NOTE: HANDRAILS AND
 GUARDRAILS ARE NOT THE SAME.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION AT TOP OF COLUMN LOCATED
 BETWEEN GARAGE AND KITCHEN. CLARIFY
 HOW IS SPECIFIED STRAP HOLDING THE
 TWO GIRDER TRUSSES. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-DETAIL R19: CLEARLY SPECIFY ALL CONNEC
 TORS. ROOF FRAMING PLAN DOESN'T SHOW
 THEM.SEC. 104.2.1.2 CITY AMENDMENTS.
 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.