Plan Review Notes
Plan Review Notes For Permit 02120171
Permit Number 02120171
Review Stop R
Sequence Number 1
Notes
Date Text
2003-01-09 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-SHEET A-1: REVISENOTE #24. SEE SEC.
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 NOTE: HANDRAILS AND GUARDRAILS ARE
 NOT THE SAME.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". AS REQ'D
 BY SEC. 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE NOTE #1. SEE SECTION
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED
 BY SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION AT
 TOP OF COLUMN LOCATED BETWEEN GARAGE
 AND KITCHEN TO SHOW HOW ARE THE TWO
 GIRDER TRUSSES ATTACHED WITH AN STRAP
 AND NOT A BUCKET CONNECTOR. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-DETAIL R19: CLEARLY SPECIFY ALL CONNEC
 TORS. ROOF FRAMING PLAN DOESN'T SHOW
 THEM. SEC. 104.2.1.2 CITY AMENDMENTS.
 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.