Plan Review Notes
Plan Review Notes For Permit 02120165
Permit Number 02120165
Review Stop R
Sequence Number 1
Notes
Date Text
2003-01-08 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8: WILL NEED TO PROVIDE
 THE ELEVATION CERTIFICATE.
 3-SHEET A-1: REVISE/CLARIFY NOTE #24.
 SEE SEC. 1007.5.1 FBC 2001.
 NOTE: HANDRAIL AND GUARDRAIL ARE NOT
 THE SAME.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE/CLARIFY NOTE #1. SEE
 SEC. 1007.5.1 FBC 2001.
 NOTE: HANDRAIL AND GUARDRAIL ARE NOT
 THE SAME.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION AT TOP OF COLUMN LOCATED
 BETWEEN GARAGE & KITCHEN. CLARIFY HOW
 IS COLUMN TOP CONNECTOR RECEIVING THE
 TWO GIRDER TRUSSES. SEE FLOOR FRAMING
 PLAN. SEC. 104.2.1.2 CITY AMENDMENTS.
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-DETAIL R19: CLEARLY SPECIFY ALL
 CONNECTORS. ROOF FRAMING PLAN DOESN'T
 SPECIFY THEM.SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.