Plan Review Notes For Permit 02120163 |
Permit Number |
02120163 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-31 00:00:00 | CHECKLIST: | | 1-REVISE/CLARIFY AREA CALCULATIONS ON | | SHEET C-1 AND A-1: TOTAL A/C AREA IS | | INCORRECT. | | 2-REVISE ENERGY CALCULATIONS A/C AREA TO | | MATCH ARCHITECT'S PLANS AFTER THEY ARE | | REVISED. | | **ALSO, REVISE UNDER ATTIC AREA. SEE | | PLANS AND SEC. 602.1ABC.1.2 OF CHAPTER | | 13 FBC 2001. | | **NOTE: DON'T FORGET A/C AREA ABOVE | | GARAGE. | | 3-SHEET A-4: HANDRAIL TO BE BETWEEN 34" | | AND 38" AS REQUIRED BY SEC. 1007.5.1 | | FBC 2001. REVISE NOTES AS REQUIRED. | | **NOTE: HANDRAIL AND GUARDRAIL ARE NOT | | THE SAME. | | 4-PROVIDE DETAIL AT CONNECTION OF THE | | WOOD SHEARWALL TO MASONRY SHEARWALL AT | | 2ND FLOOR TO SHOW HOW ARE LOADS | | TRANSFERRED. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | | | | | NOTE: | | PLEASE RETURN DRAWINGS APPROVED AND | | STAMPED BY THE OTHER TRADES TO AVOID | | HAVING TO RE-ROUTE THEM AFTER PLANS ARE | | RE-SUBMITTED. |
|