Plan Review Notes For Permit 02120162 |
Permit Number |
02120162 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-10 00:00:00 | BUILDING REVIEW PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 2-FLOOD ZONE A8. NEED TO PROVIDE THE | | ELEVATION CERTIFICATE. | | 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED | | BETWEEN GARAGE AND STAIRWAY SHOWING | | HOW IS SPECIFIED STRAP SUPPORTING THE | | TWO GIRDER TRUSSES. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | 4-REVISE CONNECTOR TC-1 SPECIFIED AT | | FRONT ELEVATION. NEED WOOD TO WOOD | | CONNECTOR FOR FRAMED WALL. SEC. 104.2. | | 1.2 CITY AMENDMENTS TO FBC 2001. | | 5-PROVIDE SPECIFICATIONS ON STRUCTURAL | | WALL SECTIONS FOR FIRECUT REQUIREMENTS | | THAT COMPLY WITH SEC. 2305.4 FBC 2001. | | 6-REVISE STAIR TOP DETAIL ON SHEET A-4 | | TO MATCH FRAMING PLAN AND SPECIFY | | FIREBLOCKING. SEC. 2305.1.4 FBC 2001. | | 7-34 SH WINDOW DOESN'T PROVIDE THE 24" | | MIN. CLEAR HEIGHT. ALSO, VERIFY THAT | | 24+5 SH WINDOW PROVIDE THE 5.7 S.F. | | MIN. CLEAR OPENING. SEC. 1005.4.4 | | FBC 2001. |
|