Plan Review Notes
Plan Review Notes For Permit 02120161
Permit Number 02120161
Review Stop R
Sequence Number 1
Notes
Date Text
2003-01-10 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED
 BETWEEN GARAGE AND STAIRWAY SHOWING
 HOW IS THE STRAP SUPPORTING THE TWO
 GIRDER TRUSSES. SETION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-REVISE CONNECTOR TC-1 SPECIFIED AT
 FRONT ELEVATION ON ROOF FRAMING PLAN.
 NEED WOOD TO WOOD CONNECTOR FOR FRAMED
 WALL. SEC. 104.2.1.2 CITY AMENDMENTS.
 5-REVISE STAIR TOP DETAIL ON SHEET A-4
 TO MATCH FRAMING PLAN AND SPECIFY
 FIREBLOCKING. SEC. 2305.1.4 FBC 2001.
 6-34 SH WINDOW DOESN'T PROVIDE THE 24"
 MIN. CLEAR HEIGHT. ALSO, VERIFY IF
 24+5 SH WINDOW PROVIDE 5.7 S.F. MIN.
 CLEAR OPENING. SEC. 1005.4.4 FBC 2001.