Plan Review Notes For Permit 02120161 |
Permit Number |
02120161 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-10 00:00:00 | BUILDING REVIEW PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 2-FLOOD ZONE A8. NEED TO PROVIDE THE | | ELEVATION CERTIFICATE. | | 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED | | BETWEEN GARAGE AND STAIRWAY SHOWING | | HOW IS THE STRAP SUPPORTING THE TWO | | GIRDER TRUSSES. SETION 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | 4-REVISE CONNECTOR TC-1 SPECIFIED AT | | FRONT ELEVATION ON ROOF FRAMING PLAN. | | NEED WOOD TO WOOD CONNECTOR FOR FRAMED | | WALL. SEC. 104.2.1.2 CITY AMENDMENTS. | | 5-REVISE STAIR TOP DETAIL ON SHEET A-4 | | TO MATCH FRAMING PLAN AND SPECIFY | | FIREBLOCKING. SEC. 2305.1.4 FBC 2001. | | 6-34 SH WINDOW DOESN'T PROVIDE THE 24" | | MIN. CLEAR HEIGHT. ALSO, VERIFY IF | | 24+5 SH WINDOW PROVIDE 5.7 S.F. MIN. | | CLEAR OPENING. SEC. 1005.4.4 FBC 2001. |
|