Plan Review Notes For Permit 02120161 |
Permit Number |
02120161 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-31 00:00:00 | ************** NOTES REDLINED ******** | | | | 1)NOTE: PLEASE CORRELATE OCP/AWG, SUB- | | -PANEL IS SHOWN W/ 40OCP ON #10AWG, | | RISER SHOWS #6`S?? | | | | PLEASE SUBMIT THE ABOVE REVISED FOR | | REVIEW BEFORE ROUGH INSPECTION IS CALLED | | IN. IF THERE ARE ANY QUESTIONS,PLEASE | | CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|