Plan Review Notes
Plan Review Notes For Permit 02120161
Permit Number 02120161
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-31 00:00:00************** NOTES REDLINED ********
  
 1)NOTE: PLEASE CORRELATE OCP/AWG, SUB-
 -PANEL IS SHOWN W/ 40OCP ON #10AWG,
 RISER SHOWS #6`S??
  
 PLEASE SUBMIT THE ABOVE REVISED FOR
 REVIEW BEFORE ROUGH INSPECTION IS CALLED
 IN. IF THERE ARE ANY QUESTIONS,PLEASE
 CALL.
  