Plan Review Notes
Plan Review Notes For Permit 02120139
Permit Number 02120139
Review Stop P
Sequence Number 1
Notes
Date Text
2002-12-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE SUBMIT A SANITARY RISER DIAG-
 RAM AND A WATER RISER DIAGRAM. SHOW ALL
 PIPE SIZES, WHERE SYSTEMS TIE INTO EXIST
 ING, AND WHERE THE VENT TIES IN. SECTION
 104.2 CHAPTER ONE FBC-2001 & AMENDMENTS
 TO BLDG CODE.
 2) DOOR TO TOILET ROOM SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE OF FIXTURES.
 20% OVER CONTRACT SHALL BE SPENT FOR
 ACCESSIBLE ISSUES PER 11-4.1.5AND
 11-4.1.6(2). PLEASE SHOW HOW THE $4,760
 WILL BE SPENT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377