Plan Review Notes
Plan Review Notes For Permit 02120137
Permit Number 02120137
Review Stop M
Sequence Number 5
Notes
Date Text
2003-06-06 00:00:00PROVISO:
  
 1.AHU SHALL HAVE OVERFLOW PROTECTION
 BY MEANS OF AN AUXILIARY DRAIN PAN WITH
 A SECONDARY DRAIN TO TERMINATE AT A
 CONSPICUOUS POINT OR FLOAT SWITCH.
  
 2.AHU UNITS SHALL HAVE SUFFICIENT
 CLEARANCE FOR ACCESS & MAINTENANCE AS
 PER 2001 FBC CHAPTER 13 610.A.ABC.3.5.2.
  
 3.CONDENSATE LINES ARE NOT SHOWN ON
 THE MECHANICAL OR PLUMBING. TERMINATION
 SHALL COMPLY WITH 2001 FBC(M) 306.2.1 &
 SHALL DISCHARGE A MINIMUM OF 12" AWAY
 FROM THE BUILDING STRUCTURE 2001 FBC
 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.