Plan Review Notes For Permit 02120137 |
Permit Number |
02120137 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2003-05-28 00:00:00 | DENIED: | | | | 1.MANUAL J CALCULATIONS WERE NOT | | SUMITTED AS PER 2001 FBC CHAPTER 13 | | SECTION 607.1.ABC.1, EQUIPMENT SIZING. | | THIS WILL BE THE 4TH REQUEST FOR THIS | | INFORMATION. | | | | PROVISO: | | 2.PLEASE NOTE, AHU SHALL HAVE OVERFLOW | | PROTECTION BY MEANS OF AN AUXILIARY | | DRAIN PAN WITH A SECONDARY DRAIN TO | | TERMINATE AT A CONSPICUOUS POINT OR | | FLOAT SWITCH. | | | | 3.AHU UNITS SHALL HAVE A SUFFICIENT | | CLEARANCE FOR ACCESS & MAINTENANCE AS | | PER 2001 FBC CHAPTER 13 610.1.ABC.3.5.2. | | | | 4.CONDENSATE LINES ARE NOT SHOWN ON | | THE MECHANICAL OR PLUMBING.TERMINATION | | SHALL COMPLY WITH 2001 FBC(M) 306.2.1 & | | SHALL DISCHARGE A MINIMUM OF 12" AWAY | | FROM THE BUILDING STRUCTURE 2001 FBC | | 1503.4.4. |
|