Plan Review Notes
Plan Review Notes For Permit 02120137
Permit Number 02120137
Review Stop M
Sequence Number 4
Notes
Date Text
2003-05-28 00:00:00DENIED:
  
 1.MANUAL J CALCULATIONS WERE NOT
 SUMITTED AS PER 2001 FBC CHAPTER 13
 SECTION 607.1.ABC.1, EQUIPMENT SIZING.
 THIS WILL BE THE 4TH REQUEST FOR THIS
 INFORMATION.
  
 PROVISO:
 2.PLEASE NOTE, AHU SHALL HAVE OVERFLOW
 PROTECTION BY MEANS OF AN AUXILIARY
 DRAIN PAN WITH A SECONDARY DRAIN TO
 TERMINATE AT A CONSPICUOUS POINT OR
 FLOAT SWITCH.
  
 3.AHU UNITS SHALL HAVE A SUFFICIENT
 CLEARANCE FOR ACCESS & MAINTENANCE AS
 PER 2001 FBC CHAPTER 13 610.1.ABC.3.5.2.
  
 4.CONDENSATE LINES ARE NOT SHOWN ON
 THE MECHANICAL OR PLUMBING.TERMINATION
 SHALL COMPLY WITH 2001 FBC(M) 306.2.1 &
 SHALL DISCHARGE A MINIMUM OF 12" AWAY
 FROM THE BUILDING STRUCTURE 2001 FBC
 1503.4.4.