Plan Review Notes
Plan Review Notes For Permit 02120137
Permit Number 02120137
Review Stop M
Sequence Number 3
Notes
Date Text
2003-05-10 00:00:00DENIED:
  
 3RD REQUEST - SUBMITT ENERGY & MANUAL J
 CALCS AS PER 2001 FBC CHAPTER 13 SECTION
 607.1.ABC.1, EQUIPMENT SIZING. AS PER
 FLORIDA STATUTE 553.80(2)(B), AFTER
 THIRD REVIEW THE PLANS ARE REJECTED FOR
 THE SAME CODE VIOLATION A FEE OF FOUR
 TIMES THE AMOUNT OF THE PORTION OF THE
 PERMIT FEE.
  
 AS PER 2001 FBC(M) TABLE 403.3, GARAGE
 SHALL HAVE A MINIMUM OF 100 CFM OUTSIDE
 AIR PER VEHICLE.PLAN SHEET M-3 THE
 EQUIPMENT SCHEDULE INDICATES
 A PROGRAMMBLE THERMOSTAT TO BE INSTALLED
 AS PER FBC CHAPTER 13, BUILDINGS(GARAGE)
 DESIGNED FOR PURPOSES OTHER THAN GENERAL
 SPACE COMFORT CONDITIONING SHALL BE
 CONTROLLED BY A HUMIDISTAT.
  
 NOTE #6, PROVIDE FRESH AIR TO EACH AHU
 GARAGES DO NOT SHOW ANY DUCT SIZE OR
 LAYOUT FOR FRSH AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.