2003-05-10 00:00:00 | DENIED: | | | | 3RD REQUEST - SUBMITT ENERGY & MANUAL J | | CALCS AS PER 2001 FBC CHAPTER 13 SECTION | | 607.1.ABC.1, EQUIPMENT SIZING. AS PER | | FLORIDA STATUTE 553.80(2)(B), AFTER | | THIRD REVIEW THE PLANS ARE REJECTED FOR | | THE SAME CODE VIOLATION A FEE OF FOUR | | TIMES THE AMOUNT OF THE PORTION OF THE | | PERMIT FEE. | | | | AS PER 2001 FBC(M) TABLE 403.3, GARAGE | | SHALL HAVE A MINIMUM OF 100 CFM OUTSIDE | | AIR PER VEHICLE.PLAN SHEET M-3 THE | | EQUIPMENT SCHEDULE INDICATES | | A PROGRAMMBLE THERMOSTAT TO BE INSTALLED | | AS PER FBC CHAPTER 13, BUILDINGS(GARAGE) | | DESIGNED FOR PURPOSES OTHER THAN GENERAL | | SPACE COMFORT CONDITIONING SHALL BE | | CONTROLLED BY A HUMIDISTAT. | | | | NOTE #6, PROVIDE FRESH AIR TO EACH AHU | | GARAGES DO NOT SHOW ANY DUCT SIZE OR | | LAYOUT FOR FRSH AIR. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|