Plan Review Notes
Plan Review Notes For Permit 02120137
Permit Number 02120137
Review Stop M
Sequence Number 2
Notes
Date Text
2003-03-31 00:00:00DENIED:
  
 COMMENTS FROM 1ST REVIEW NOT ADDRESSED.
 PROVIDE MANUAL J CALCS AS PER 2001 FBC
 CHAPTER 13 SECTION 607.1.ABC.1,
 EQUIPMENT SIZING.PROVIDE INFORMATION
 OF HVAC EQUIPMENT (MAKE, MODEL, BTU OF
 THE AHU & SEER OF THE CONDENSING UNIT).
  
 NO MECHANICAL PLANS INDICATING DUCT LAY-
 OUT OF LOCATION OF AHU'S OR CONDENSING
 UNITS SUBMITTED FOR REVIEW.
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.