Plan Review Notes
Plan Review Notes For Permit 02120137
Permit Number 02120137
Review Stop E
Sequence Number 2
Notes
Date Text
2003-03-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} THERE ARE NO SMOKE DETECTORS ON
 SHEET E-4.PLEASE SHOW COMPLIANCE WITH
 8-1.4.1.6 NFPA-72.
  
 2} PLEASE NOTE THAT THE PANELS SHOWN IN
 THE CLOSET ON SHEET E-3(A,B,C,SB,AND
 LV'S) MUST COMPLY WITH110-26.
  
 3} THE SMOKE DETECTOR @ THE DOORWAY
 OF THE MASTER BEDROOM JUST AT THE
 HALL APPEARS TO BE INSIDE THE AREA OF
 THE MASTER BEDROOM AND WOULD THEREFORE
 NOT BE IN COMPLIANCE WITH 8-1.4.2
 NFPA-72,AS BEING LOCATED "OUTSIDE".
  
 THESE THREE COMMENTS WERE ON THE LAST
 REVIEW,IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096.EXT 8392.