Plan Review Notes
Plan Review Notes For Permit 02120137
Permit Number 02120137
Review Stop B
Sequence Number 2
Notes
Date Text
2003-04-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120137
 ADD: 3400 N FLAGLER DR
 CONT:(PLAN REVIEW/ 2ND REVIEW)
 SANDERSON, MARK & FREDI
 CONTACT: LYNNE GILLIS
 TEL: (561)346-4249
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTES:
 1) FLOOD ZONE A5 MINIMUM ELEVATION 7.5'
 FOR FINISH FLOOR, A/C PADS AND POOL
 EQUIPMENT PADS (ELEC MOTORS). A FLOOD
 ZONE ELEVATION CERTIFICATE IS REQUIRED
 TO THIS DEPARTMENT BEFORE A C/O WILL BE
 ISSUED.
  
 2) NO BUILDING IN THE EASEMENTS SOUTH
 PROPERTY LINE INDICATES A 10' SEWER &
 DRAINAGE EASEMENT W / A 60" RCP PIPE.
  
  
 REVIEW:
 1) 1803.1.3 EXCAVATION FOR ANY PURPOSE S
 HALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NATURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
  
 THE DETAIL PROVIDED BY BOTKIN ON
 SHEET S-5 DETAIL 13 DOESN'T INCLUDE THE
 1'=0" BEFORE THE ANGLE OF REPOSE, WHEN
 THE 1'-0" IS INCLUDED THE PIPE IS 1'-0"
 HIGHER IN THE TRENCH!
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCIES: ARCH PLAN, THE FAMILY
 ROOM FLOOR ELEVATION, HALL 117 & CABANA
 ARE INDICATED AS A 10'-0" F.F. DOORS
 6,7 & 8 INDICATE A SIX INCH DROP BUT
 DOOR # 10 IS MISSING THIS 6" DROP.
  
 THE SECOND ISSUE BETWEEN IN THIS SAME
 TERRACE FLOOR, ARCH PLANS INDICATE A
 6" DROP WHERE AS THE STRUCTURAL PLAN
 INDICATE A 4" DROP W/ 2" SLOPE?
  
 4) SHEET A-8 & A-11 EAST ELEVATION
 RE: GUARDRAILS 1026.5.1 TRUE GUARDRAILS
 FOR DWELLINGS, WITHIN INDIVIDUAL DWELL-
 ING UNITS OR GUEST ROOMS,AND IN RESIDENT
 IAL CARE/ ASSISTED LIVING OCCUPANCIES
 SHALL BE A MINIMUM OF 36" IN HEIGTH.
  
 1015.1 GUARDRAILS SHALL FORM A VERTICAL
 PROTECTIVE BARRIER NOT LESS THAN 42"
 HIGH.
  
 GUARDRAILS ON THE EXTERIOR OF THE BUILD-
 ING DO NOT HAVE THE EXCEPTION THAT MAY
 BE TAKEN IN 1026.5.1.
  
 5) 1606.5 COMPONENTS & CLADDING:
 INDICATE PRESSURE ZONES POSITIVE &
 NEGATIVE FOR (INTERIOR & END ZONES).
 INDICATE PRESSURES ON ELEVATIONS.
  
 BECAUSE THIS COMMENT WAS NOT ANSWERED
 THE PRODUCT TESTING REPORTS CAN NOT BE
 EVALUATED!!!!!
  
 PROVIDE (2) COPIES OF ALL PRODUCT TEST-
 ING REPORTS.
  
 6)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. THIS INFORMATION IS
 SUPPLIED BY THE CONTRACTOR USUALLY!
 MISSING REPORTS:
 A) GARAGE DOORS OVERHEAD, HIGHLIGHT AS
 TO WHICH DOOR THAT WILL BE SELECTED
 WITH THE APPROPRIATE DESIGN LOADS.
 B) SWING DOORS GLAZED & SOLID
 MISSINGTHE SOLID EXTERIOR DOOR
 REPORTS. EXAMPLE DOOR 15 OR 18
 C) WINDOWS, CASEMENT, FIXED, OR THE
 LEADED GLASS.
 A SEPERATE SHEET IS PROVIDED WITH
 ALL OF THE MARVIN WINDOWS & DOORS.
 SEPERATE NOA (NOTICE OF ACCEPTANCE)
 WILL BE REQUIRED FOR EACH APPLICA-
 TION, PROVIDE (2) COPIES PLEASE.
 D) MULLION: BOTH VERTICAL AND HORIZON-
 TAL APPLICATIONS REQUIRED.
 E) STORM SHUTTERS IF THE PRODUCT TEST-
 ING REPORTS HAVEN'T RECEIVED APPROV-
 AL FOR LARGE MISSLE IMPACT TESTING.
  
 8)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 9)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 10)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 11)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. SEE ATTACHMENT IF REQUIRED.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved