2003-01-21 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE PROVIDE THE FOLLOWING |
| INFORMATION,MAKE ANY NECESSARY CHANGE |
| ON PLANS AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE NOTE THAT ALL PLANS |
| THAT ARE SIGNED AND SEALED BY ARCH/ OR |
| ENGINEER ARE REQ`D PER 61G15-23.002 FOR |
| ENGINEER AND 61G1-16.004 FOR ARCH. |
| SHALL HAVE A TITLE BLOCK. |
| |
| 2} PLEASE INDICATE THE AMPERE RATING OF |
| THE METER ENCLOSURE. |
| |
| 3} PLEASE INDICATE THE CONDUCTOR AND |
| WIRE SIZE FROM THE METER TO THE M.D.P. |
| |
| 4} THE FEEDER CONDUCTORS TO PANEL "N" |
| ARE SHOWN AS NUMBER 1 ON MDP SCHEDULE |
| AND 2/0'S ON THE RISER DIAGRAM.PLEASE |
| CLARIFY. |
| |
| 5} THE FEEDER CONDUCTORS TO PANEL "C" |
| ARE SHOWN AS 3/0'S ON THE PANEL |
| SCHEDULE AND 2/0 ON THE RISER |
| DIAGRAM,PLEASE CLARIFY. |
| |
| 6} THERE ARE NO SMOKE DETECTORS ON |
| SHEET E4.PLEASE SHOW COMPLIANCE WITH |
| 8-1.4.1.6 NFPA-72. |
| |
| 7} PLEASE NOTE THAT THE PANELS SHOWN IN |
| THE CLOSET ON SHEET E3(A,B,C,SB AND LV'S |
| MUST COMPLY WITH 110-26. |
| |
| 8} THE SMOKE DETECTOR @ THE DOORWAY OF |
| THE MASTER BEDROOM JUST AT THE |
| HALL,APPEARS TO BE INSIDE THE AREA OF |
| THE MASTER BEDROOM AND WOULD THEREFORE |
| NOT BE IN COMPLIANCE 8-1.4.2 NFPA-72,AS |
| BEING LOCATED "OUTSIDE". |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |