Plan Review Notes
Plan Review Notes For Permit 02120132
Permit Number 02120132
Review Stop M
Sequence Number 3
Notes
Date Text
2003-07-08 00:00:00PROVISO:
  
 PLAN SHEET M2.2, THE WALL BETWEEN THE
 BREAK ROOM AND STORAGE ROOM HAS A 1 HR
 RATING, AS PER 2001 FBC(M) 607.1.3
 EXCEPTIONS - FIRE DAMPERS ARE NOT
 REQUIRED UNDER THE FOLLOWING CONDITIONS:
 #3 ITEMS 1 THROUGH 4 AS FOLLOWS
 1. DUCTS DO NOT EXCEED 100 SQ INCHES
 2. DUCT SHALL BE A MINIMUM OF .0217 INCH
 STEEL
 3. DUCT SHALL CONTINUE WITH NO DUCT
 OPENINGS FOR NOT LESS THAN 5 FT FROM
 THE RATED WALL
 4. THE DUCT SHALL BE ISNTALLED ABOVE THE
 CEILING
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.