Plan Review Notes For Permit 02120132 |
Permit Number |
02120132 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-07-08 00:00:00 | PROVISO: | | | | PLAN SHEET M2.2, THE WALL BETWEEN THE | | BREAK ROOM AND STORAGE ROOM HAS A 1 HR | | RATING, AS PER 2001 FBC(M) 607.1.3 | | EXCEPTIONS - FIRE DAMPERS ARE NOT | | REQUIRED UNDER THE FOLLOWING CONDITIONS: | | #3 ITEMS 1 THROUGH 4 AS FOLLOWS | | 1. DUCTS DO NOT EXCEED 100 SQ INCHES | | 2. DUCT SHALL BE A MINIMUM OF .0217 INCH | | STEEL | | 3. DUCT SHALL CONTINUE WITH NO DUCT | | OPENINGS FOR NOT LESS THAN 5 FT FROM | | THE RATED WALL | | 4. THE DUCT SHALL BE ISNTALLED ABOVE THE | | CEILING | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|