2003-03-25 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 THE SUBMITTED STORE FRONT DOOR PRODUCT
 APPROVAL NOA# 01-0919.02 IS FOR SINGLE
 UNIT APPLICATIONS ONLY, AND SO DOES NOT
 COVER THE MULLED SIDELITES ADJACENT
 DOOR #1.STRUCTURAL MULLIONS ARE
 REQUIRED. ALSO, THE SIDELITES EXCEED THE
 96" MAX. HEIGHT COVERED BY THE WINDOW
 WALL SYSTEM PRODUCT APPROVAL
 NOA# 01-0329.02, SO A HORIZONTAL MULLION
 IS REQUIRED.SUBMIT AN APPROPRIATE
 STRUCTURAL MULLION PRODUCT APPROVAL OR
 SITE SPECIFIC ENGINEERING.