Plan Review Notes For Permit 02120132 |
Permit Number |
02120132 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-03-25 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | --PROVISO-- | | THE SUBMITTED STORE FRONT DOOR PRODUCT | | APPROVAL NOA# 01-0919.02 IS FOR SINGLE | | UNIT APPLICATIONS ONLY, AND SO DOES NOT | | COVER THE MULLED SIDELITES ADJACENT | | DOOR #1.STRUCTURAL MULLIONS ARE | | REQUIRED. ALSO, THE SIDELITES EXCEED THE | | 96" MAX. HEIGHT COVERED BY THE WINDOW | | WALL SYSTEM PRODUCT APPROVAL | | NOA# 01-0329.02, SO A HORIZONTAL MULLION | | IS REQUIRED.SUBMIT AN APPROPRIATE | | STRUCTURAL MULLION PRODUCT APPROVAL OR | | SITE SPECIFIC ENGINEERING. |
|