Plan Review Notes
Plan Review Notes For Permit 02120132
Permit Number 02120132
Review Stop P
Sequence Number 2
Notes
Date Text
2003-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW, SHT PO.1 THERM-
 AL EXPANSION CONTROL REQUIRED PER SEC.
 607.3.2. PLEASE SHOW ON W/H'S #1 & #2.
 SHEETS WERE NOT CHANGED.
 2) FROM PREVIOUS REVIEW, SHT P6.1 WATER
 RISER DIAGRAM, WATER HAMMER ARRESTORS
 REQUIRED BY SEC 604.9 SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT AT THE TOP OF DROPS IN THE CEILING
 AS SHOWN. PDI-WH 201 AND MANUF. INSTALL-
 ATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377