Plan Review Notes
Plan Review Notes For Permit 02120132
Permit Number 02120132
Review Stop P
Sequence Number 1
Notes
Date Text
2002-12-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) STH A.7 PRIVATE TOILET ROOM FOR EXEC.
 SHALL BE ADAPTABLE PER 11-4.1.3(11).
 SHOW DETAIL FOR GRAB BAR BACKING, OPEN-
 ING FOR W/C, LAV HEIGHT (34") ECT.
 2) SHT A.9 BREAK ROOM ELEVATIONS #'S 1 &
 2. SINKS SHALL COMPLY WITH 11-4.24 AND
 ALL SUBSECTIONS. PLEASE SHOW DETAILS.
 3) SHT P0.1 THERMAL EXPANSION CONTROL
 REQUIRED PER SEC 607.3.2. PLEASE SHOW
 ON WATER HEATER DETAIL EWH #1 & EWH #2.
 4) SHT P2.1 - RELIEF VENT REQUIRED ON
 CONDENSATE LINE AS IT EXITS BLDG.
 5) SHT P6.1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED BY 604.9 SHALL
 BE LOCATED NEAR THE FIXTURES IN AN
 "EFFICTIVE RANGE" NOT AT TOP OF DROPS IN
 CEILING AS SHOWN.
  