Plan Review Notes For Permit 02120132 |
Permit Number |
02120132 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-19 00:00:00 | 1) THE PROPOSED FIRE HYDRANT IS TO MEET | | UTILITY AND FIRE RESCUE STANDARDS. | | TYPICALLY, THE CITY DOES NOT USE THE | | COLOR RED FOR FIRE HYDRANTS. | | | | 2) ELECTRONIC SWITCHES WILL BE REQUIRED | | ON BACKFLOW DEVICES THAT CONTROL FIRE | | LINE SERVICE. | | | | 3) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | 4) PLEASE PROVIDE A LIFE SAFETY PLAN | | INDICATING OCCUPANT LOADS AND TRAVEL | | DISTANCES. ALSO PLEASE DEMONSTRATE | | COMPLIANCE WITH EXIT SEPARATION | | REQUIREMENTS OF AT LEAST 1/2 THE | | DIAGONAL DISTANCE SINCE NO FIRE | | SPRINKLER SYSTEM IS PLANNED. | | | | 5) A REMOTE FIRE ALARM ANNUNCIATOR | | APPEARS TO BE REQUIRED AT THE FRONT | | ENTRYWAY. | | | | 6) SINCE NO FIRE SPRINKLERS ARE PLANNED, | | ALL ELECTRICAL,MECHANICAL, AND STORAGE | | ROOMS ARE TO BE AT LEAST ONE HOUR | | FIRE RATED WITH RATED OPENING | | PROTECTIVE DEVICES. | | | | 7) AN EXIT SIGN IS MISSING INFRONT OF | | STAIR # 2, FIRST FLOOR. | | | | 8) A KNOX-BOX WILL BE REQUIRED FOR | | THE BUILDING. | | | | 9) NO BUILDING ELEVATION DRAWINGS | | PROVIDED. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|