Plan Review Notes For Permit 02120132 |
Permit Number |
02120132 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-26 00:00:00 | **************** UNSAT ************** | | | | 1)NOTE:PLEASE SEE E2.1, SOME CIRCUITS | | MISSING CIRCUIT | | DESIGNATION. | | | | 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | THAT WILL AHVE AN AFFECT ON ELECTRICAL | | SHEETS. | | | | 3)NOTE: PLEASE NOTE/CLARIFY LTS FIXTURES | | IN ELEV /ELEC ROOMS TO MEET 700-16 | | | | | | | | | | | | | | | | | | | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPENT. 110-9/215-5 | | | | 7)NOTE: PLEASE SHOW SIZE OF METERCAN | | "H1A".? | | | | 8)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS | | ARE TO BE SHOWN AT 125%. 215-3/230-42 ET | | C. | | | | 9)NOTE: PLEASE SEE WATER HEATER ON H2A | | 2P-30A W/ #12`S, PLEASE SIZE WIRE PER | | 310-16 | | | | 10)NOTE: PLEASE NOTE "L2B" IS REQ`D TO | | HAVE A MCB ON LOAD SIDE OF TRANSFORMER | | 384-16,240-21 | | | | 11)NOTE: PLEASE SHOW MIN LOAD FOR | | FUTURE TENANT SPACE AND HOW LOAD WAS | | FIGURED. | | | | 12)NOTE: PLEASE CLARIFY WHERE LPA PANEL | | SCHEDULE IS SHOWN? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|