2003-01-16 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) FBC* 1804.2.2SUBMIT A GEOTECHNICAL |
| REPORT. |
| |
| 4) FBC* 104.1.1A SEPARATE PERMIT |
| APPLICATION WILL BE REQUIRED FOR THE |
| DUMPSTER ENCLOSURE. |
| |
| 5) SUBMIT PRODUCT APPROVALS FOR THE |
| EXTERIOR DOORS, WINDOWS AND ROOFING. |
| |
| 6) FBC 13-103.1.2BEFORE A BUILDING |
| PERMIT CAN BE ISSUED, THE SUBMITTED |
| ENERGY CODE COMPLIANCE FORMS SHALL BE |
| SIGNED BY THE BUILDING OWNER, THE |
| OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| AGENT LEGALLY DESIGNATED BY THE OWNER. |
| ***NOTE: ADD THE FULL STREET ADDRESS, |
| 2130 CENTREPARK DRIVE W, TO THE PROJECT |
| INFORMATION SECTION OF EACH COPY OF THE |
| COMPLIANCE FORM BEFORE RESUBMITTING. |
| |
| 7) FBC 1004.1.4ARRANGEMENT OF EXITS. |
| THE STRAIGHT LINE DISTANCE BETWEEN THE |
| SECOND FLOOR EXIT DOORS SHALL NOT BE |
| LESS THAN 1/2 THE LENGTH OF THE MAXIMUM |
| DIAGONAL DIMENSION OF THE BUILDING, |
| WHICH IS APPROX. 155 FT.AMEND THE |
| PLANS TO ACHIEVE COMPLIANCE. |
| |
| 8) FBC 11-4.1.3(9)AREAS OF RESCUE |
| ASSISTANCE ARE REQUIRED BECAUSE THE |
| BUILDING IS NOT SPRINKLERED.AMEND THE |
| PLANS TO IDENTIFY LOCATIONS.ONE OPTION |
| IS TO PROVIDE DETAILS TO SHOW THAT THE |
| STAIR #2 LANDING AND THE ELEVATOR |
| LOBBY #2, ADJACENT STAIR #1, COMPLY WITH |
| THE REQUIREMENTS OF FBC 11-4.3.11.1. |
| NOTE: IF STAIR #1 IS REVERSED, THEN THAT |
| LANDING COULD BE USED INSTEAD OF HAVING |
| TO UPGRADE THE ELEVATOR LOBBY TO MEET |
| THE REQUIREMENTS FOR AN AREA OF RESCUE |
| ASSISTANCE. |
| |
| 9) FBC 4.3.11.3STAIRWAY WIDTH. AS PART |
| OF THE REQUIREMENTS FOR AREAS OF RESCUE |
| ASSISTANCE IN A NON-SPRINKLERED |
| BUILDING, THE STAIRWAYS SHALL HAVE A |
| CLEAR WIDTH OF 48" BETWEEN HANDRAILS. |
| |
| 10) FBC 4.3.11.4TWO-WAY COMMUNICATION |
| IS REQUIRED BETWEEN THE AREAS OF RESCUE |
| ASSISTANCE AND THE PRIMARY ENTRANCE. |
| |
| 11) FBC 705.1.2EXIT DOORS.THE DOORS |
| TO THE STAIR #1 AND #2 ENCLOSURES AND TO |
| THE FIRST FLOOR LOBBY (SHEET A.6DOOR |
| SCHEDULE MARKS 2, 4 AND 19) ARE REQUIRED |
| TO PROVIDE 1 HOUR FIRE RESISTANCE. |
| AMEND THE DOOR SCHEDULE TO SHOW THIS |
| REQUIREMENT. |
| |
| 12) FBC 11-4.13.6 MANEUVERING CLEARANCES |
| AT DOORS.THE LEADING EDGE OF THE DOORS |
| TO 'OFFICE 4' (DOOR 9) AND 'BREAK 1' |
| (DOOR 7) AND 'CUSTOMER AREA' (DOOR 7) ON |
| THE FIRST FLOOR SHALL NOT BE LESS THAN |
| 18" FROM THE ADJACENT WALL ON THE PULL |
| SIDE OF THE DOOR. |
| |
| 13) FBC 11.4.9.4(2)SHEET A.4, TYPICAL |
| STAIR DETAILS.THE STAIR HANDRAIL SHALL |
| EXTEND AT LEAST 12" HORIZONTALLY BEYOND |
| THE TOP RISER, AND SHALL CONTINUE TO |
| SLOPE PAST THE BOTTOM RISER , FOR A |
| DISTANCE EQUAL TO THE WIDTH OF ONE |
| TREAD, AND THEN EXTEND A FURTHER 12" |
| HORIZONTALLY AT THE BOTTOM. |
| |
| 14) FBC 11-4.15DRINKING FOUNTAINS. |
| THE ELEVATIONS ON SHEET A.7 DO NOT SHOW |
| THE HEIGHT AND THE LEG CLEARANCES FOR |
| DRINKING FOUNTAINS.AMEND/SUBMIT PLANS, |
| FOR THE FIRST AND SECOND FLOOR DRINKING |
| FOUNTAINS, TO DEMONSTRATE COMPLIANCE |
| WITH THE REQUIREMENTS OF FIG. 27. |
| |
| 15) FBC 11-4.16.3 & 4W.C. HEIGHT AND |
| GRAB BARS.THE ELEVATIONS ON SHEET A.7 |
| DO NOT SHOW THE W.C. HEIGHT AND GRAB BAR |
| PLACEMENT.AMEND/SUBMIT PLANS TO |
| DEMONSTRATE COMPLIANCE WITH THE FIG. 29 |
| REQUIREMENTS FOR ACCESSIBLE W.C'S. |
| |
| 16) SHEET A.5, FIRST FLOOR WINDOWS.THE |
| NORTH END OF THE WEST ELEVATION SHOWS |
| TWO FIRST FLOOR WINDOWS WHICH ARE NOT |
| SHOWN ON THE FIRST FLOOR PLAN. |
| |
| 17) SHEET S.6, SECTION 3, WOOD GABLE END |
| TRUSS ANCHORING.FROM SIMPSON PRODUCT |
| LITERATURE IT APPEARS THAT THE PROPOSED |
| HUC26 ANCHORS MAY NOT HAVE SUFFICIENT |
| CAPACITY FOR A 24 FT SPAN TRUSS WITH |
| THIS TRIBUTARY WIDTH (APPROX. 1'-4" PLUS |
| THE DEPTH OF THE PROFILE 3 PARAPET CAP). |
| ADD THE CALCULATED UPLIFT TO THE PLANS |
| FOR CROSS REFERENCE AGAINST THE PROPOSED |
| ANCHOR. |
| |
| 18) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| OLD SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHALL BE INCLUDED WITH THE |
| RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |