Plan Review Notes For Permit 02120125 |
Permit Number |
02120125 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-09 00:00:00 | PROVISO: | | | | 1.ACCESS OPENING FOR THE AHU IN ATTIC | | SHALL BE NO LESS THAN 20" X 30" CLEAR | | ACCESS. | | | | 2.DRAIN PAN WITH OVERFLOW PROTECTION | | REQUIRED AS PER 2001 FBC(M) 307.2.3. | | | | 3.RETURN AIR OR TRANSFER AIR REQUIRED | | FROM BEDROOM AREAS, 2001 FBC(M) 601.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|