2003-08-22 00:00:00 | ************PROVISO/NOTE ********** | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | AND ALL PANELS. A/C SUB PANEL NOT SHOWN | | ON RISER. | | | | 2)NOTE: PLEASE SHOW CONDUITS FROM METER | | TO PANELS AS INSTALLED IN SLAB. | | 210.70 | | | | 3)NOTE: PLEASE VERIFY KW RATINGS FOR | | AHU'S, SHOWS 5KW UNIT ON 2P60A? IF 10KW | | UNIT, REVISE LOAD CALCUALTIONS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW BEFORE FINAL ELEC/CO. PARTIAL | | FINAL ELECTRICAL IS OK. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|