Plan Review Notes
Plan Review Notes For Permit 02111972
Permit Number 02111972
Review Stop R
Sequence Number 1
Notes
Date Text
2003-01-17 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE ENERGY CALCULATIONS.
 2-PROVIDE SOIL TEST REPORT.
 3-PROVIDE PAID IMPACT FEES RECEIPT.
 4-PROVIDE NOTICE OF COMMENCEMENT.
 5-REVISE STRUCTURAL DETAIL FOR 2X DOOR
 BUCK. SEE SEC. 1707.4.4.2 FBC 2001.
 6-PROVIDE COMPLETE STRUCTURAL DETAIL FOR
 WATER HEATER PROTECTION BOLLARD. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-BLDG SECTION A-A ON SHEET A-3 CALLS
 FOR 6"RECESS AT FRONT &BACK PORCHES.
 SPECIFY HOW IS THE FOOTING GOING TO BE
 12" BELOW GRADE AS REQUIRED BY SECTION
 1804.1.3 FBC 2001 IF THE FOOTING IS
 16" DEEP.
 8-PROVIDE COMPLETE SPECS FOR GARAGE DOOR
 STRUCTURAL BUCK DETAIL. EG: MISSING
 SPECS FOR WASHER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 9-USP TA20 STRAP SPECIFIED FOR 3(2X4)COL
 IS FOR CONCRETE APPLICATION. NEED WOOD
 TO WOOD CONNECTOR. REVISE AS REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-REVISE ANCHOR SCHEDULE TO MATCH USP
 PUBLISHED VALUES ACCORDING TO SIZE AND
 NUMBER OF NAILS OR PROVIDE ENGINEERING
 CALCULATIONS FOR DIFFERENT VALUES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 **NOTE: KEEP IN MIND THAT NEED 1 3/4"
 EMBEDMENT INTO WOOD TO GET THE FULL
 VALUES. SEE FOOTNOTE ON USP CATALOGUE.
 11-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 12-SEE COMMENTS BY MECHANICAL REVIEWER.
 13-PROVIDE PRODUCT APPROVAL FOR:
 A)FIXED WINDOWS THAT MATCH THE BIG SIZES
 SHOWN ON PLANS.
 B)STRUCTURAL MULLIONS FOR LONG SIZES AS
 SHOWN ON PLANS.
 C)ENTRY DOOR W/ SIDELITE SINGLE ASSEMBLY
 AS SHOWN ON PLANS & W/ LEGIBLE DWGS.
 D)ROOF TILE PRODUCT APPROVAL EXPIRED.
 PROVIDE UPDATED ONE.
  
 14-STORM SHUTTERS:
 A)PROVIDE KEY PLAN & INSTALLATION SCHED.
 THAT MATCHES PLANS. EG: SEE PANELS 1,2
 B)CHECK APPROVED DRAWINGS FOR MINIMUM
 AND MAXIMUM PANEL SIZE.
 C)STORM SHUTTERS COVER PAGE:
 **SEE PLANS FOR CORRECT MEAN ROOF HEIGHT
 **PRODUCT APPROVAL SUBMITTED IS FROM
 SBCCI, NOT DADE COUNTY.
 D)CLEARLY MARK ON APPROVED DRAWINGS
 THE SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE MEAN ROOF HEIGHT,
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO.
 E)SEE LIMITATIONS ON PAGE 3 OF 3 OF
 PRODUCT APPROVAL FOR ANCHORS TO BE
 USED.
 **NOTE: IF INFORMATION IS NOT COMPLETE
 AT TIME OF RESUBMITTAL CONTRACTOR MAY
 APPLY FOR STORM PANELS SEPARATE TO
 AVOID DELAYING BUILDING PERMIT.