2003-01-17 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-PROVIDE ENERGY CALCULATIONS. |
| 2-PROVIDE SOIL TEST REPORT. |
| 3-PROVIDE PAID IMPACT FEES RECEIPT. |
| 4-PROVIDE NOTICE OF COMMENCEMENT. |
| 5-REVISE STRUCTURAL DETAIL FOR 2X DOOR |
| BUCK. SEE SEC. 1707.4.4.2 FBC 2001. |
| 6-PROVIDE COMPLETE STRUCTURAL DETAIL FOR |
| WATER HEATER PROTECTION BOLLARD. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 7-BLDG SECTION A-A ON SHEET A-3 CALLS |
| FOR 6"RECESS AT FRONT &BACK PORCHES. |
| SPECIFY HOW IS THE FOOTING GOING TO BE |
| 12" BELOW GRADE AS REQUIRED BY SECTION |
| 1804.1.3 FBC 2001 IF THE FOOTING IS |
| 16" DEEP. |
| 8-PROVIDE COMPLETE SPECS FOR GARAGE DOOR |
| STRUCTURAL BUCK DETAIL. EG: MISSING |
| SPECS FOR WASHER. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 9-USP TA20 STRAP SPECIFIED FOR 3(2X4)COL |
| IS FOR CONCRETE APPLICATION. NEED WOOD |
| TO WOOD CONNECTOR. REVISE AS REQUIRED. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 10-REVISE ANCHOR SCHEDULE TO MATCH USP |
| PUBLISHED VALUES ACCORDING TO SIZE AND |
| NUMBER OF NAILS OR PROVIDE ENGINEERING |
| CALCULATIONS FOR DIFFERENT VALUES. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| **NOTE: KEEP IN MIND THAT NEED 1 3/4" |
| EMBEDMENT INTO WOOD TO GET THE FULL |
| VALUES. SEE FOOTNOTE ON USP CATALOGUE. |
| 11-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| SEE PLANS AND SEC. 2405.2 FBC 2001. |
| 12-SEE COMMENTS BY MECHANICAL REVIEWER. |
| 13-PROVIDE PRODUCT APPROVAL FOR: |
| A)FIXED WINDOWS THAT MATCH THE BIG SIZES |
| SHOWN ON PLANS. |
| B)STRUCTURAL MULLIONS FOR LONG SIZES AS |
| SHOWN ON PLANS. |
| C)ENTRY DOOR W/ SIDELITE SINGLE ASSEMBLY |
| AS SHOWN ON PLANS & W/ LEGIBLE DWGS. |
| D)ROOF TILE PRODUCT APPROVAL EXPIRED. |
| PROVIDE UPDATED ONE. |
| |
| 14-STORM SHUTTERS: |
| A)PROVIDE KEY PLAN & INSTALLATION SCHED. |
| THAT MATCHES PLANS. EG: SEE PANELS 1,2 |
| B)CHECK APPROVED DRAWINGS FOR MINIMUM |
| AND MAXIMUM PANEL SIZE. |
| C)STORM SHUTTERS COVER PAGE: |
| **SEE PLANS FOR CORRECT MEAN ROOF HEIGHT |
| **PRODUCT APPROVAL SUBMITTED IS FROM |
| SBCCI, NOT DADE COUNTY. |
| D)CLEARLY MARK ON APPROVED DRAWINGS |
| THE SPECIFIC MOUNTING CONDITIONS AND |
| ANCHOR TYPE AND SPACING TO BE USED |
| ACCORDING TO THE MEAN ROOF HEIGHT, |
| DESIGN PRESSURES, EDGE DISTANCE, PANEL |
| SPAN, CONNECTION TYPE AND STRUCTURE TO |
| BE ATTACHED TO. |
| E)SEE LIMITATIONS ON PAGE 3 OF 3 OF |
| PRODUCT APPROVAL FOR ANCHORS TO BE |
| USED. |
| **NOTE: IF INFORMATION IS NOT COMPLETE |
| AT TIME OF RESUBMITTAL CONTRACTOR MAY |
| APPLY FOR STORM PANELS SEPARATE TO |
| AVOID DELAYING BUILDING PERMIT. |