2002-12-27 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | ***********SHELL ONLY*********** | | | | 1) PLEASE SUPPLY CALCULATIONS FOR PRI- | | MARY AND SECONDARY ROOF DRAINS. SQUARE | | FOOTAGE FOR EACH DRAIN SHOWS THE SAME | | BUT SHEET A-5 SHOWS SECTION A-B DRAINING | | LESS AREA THAN SECTION B THRU D, AND | | SECTION D THRU F. SECTION F THRU G WILL | | DRAIN LESS THEN SECTIONS B THRU D AND | | SECTION F THRU G. EACH SECTION SHALL | | BE CALCULATED SEPARATE ACCORDING TO AREA | | OF ROOF THAT DRAINS INTO DRAIN. ALSO | | INCLUDE 1/2 AREA OF VERTICAL WALL INTO | | SQUARE FOOTAGE PER SEC 1106.4. | | 2) SHEET A-5 REFERENCES SHEET A-15, BUT | | SHEET A-15 NOT INCLUDED IN PLANS. PLEASE | | CLAIRFY. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|