2002-12-11 00:00:00DENIED:
  
 PROVIDE DETAIL FOR THE EXHAUST FAN
 CURBS. SHOW ATTACHMENT DETAILS.
  
 EXHAUST SHALL NOT BE DIRECTED ONTO
 WALKWAYS AS PER 2001 FBC(M) 401.5.1.
  
 PLAN SHEET M0.1 DETAIL - LOUVER LOCATION
 IS THIS LOUVER MAKE-UP AIR?PLEASE
 CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.