Plan Review Notes
Plan Review Notes For Permit 02111908
Permit Number 02111908
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-09 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE LOAD ON PANEL "1HP"
 PLEASE NOTE, LOAD EXCEEDS RATING OF
 CONDUCTORS.
  
 2)NOTE: PLEASE SHOW SIZE OF DISCONNECTS
 AND SHOW SIZE OF OCP. NOE SHOWN FOR 1HP?
  
 3)NOTE: PLEASE PROVIDE NOTE ON FIRE
 PUMP RISER, OCP TO MEET 695-4B-1
  
 4)NOTE: PLEASE SEE MAINS 1 AND 2, BOTH
 SHOWN WITH 1000A FUSES ON 800A MAINS???
 PLEASE NOTE IF MAINS ARE GOING TO BE
 1000A, GFI PROTECTION PER 230-95 MUST BE
 MET. PLEASE CORRELATE.
  
 5)NOTE: PLEASE CLARIFY LIGHTING IN
 BLDG, ONLY EM/EXT LTS SHOWN?
  
 6)NOTE: PLEASE SHOW LOCATION OF FIRE
 PUMP ROOM. PLEASE NOTE GROUPING OF MAINS
 230-72, PLEASE CLARIFY TRAVEL DISTANCE
 FROM MAIN ELECTRICAL ROOM.
  
 7)NOTE: PLEASE CLARIFY LIGHTING TO MEET
 700-16. PLEASE ALSO SEE 700-12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  