Plan Review Notes For Permit 02111908 |
Permit Number |
02111908 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-09 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE SEE LOAD ON PANEL "1HP" | | PLEASE NOTE, LOAD EXCEEDS RATING OF | | CONDUCTORS. | | | | 2)NOTE: PLEASE SHOW SIZE OF DISCONNECTS | | AND SHOW SIZE OF OCP. NOE SHOWN FOR 1HP? | | | | 3)NOTE: PLEASE PROVIDE NOTE ON FIRE | | PUMP RISER, OCP TO MEET 695-4B-1 | | | | 4)NOTE: PLEASE SEE MAINS 1 AND 2, BOTH | | SHOWN WITH 1000A FUSES ON 800A MAINS??? | | PLEASE NOTE IF MAINS ARE GOING TO BE | | 1000A, GFI PROTECTION PER 230-95 MUST BE | | MET. PLEASE CORRELATE. | | | | 5)NOTE: PLEASE CLARIFY LIGHTING IN | | BLDG, ONLY EM/EXT LTS SHOWN? | | | | 6)NOTE: PLEASE SHOW LOCATION OF FIRE | | PUMP ROOM. PLEASE NOTE GROUPING OF MAINS | | 230-72, PLEASE CLARIFY TRAVEL DISTANCE | | FROM MAIN ELECTRICAL ROOM. | | | | 7)NOTE: PLEASE CLARIFY LIGHTING TO MEET | | 700-16. PLEASE ALSO SEE 700-12E | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|