Plan Review Notes
Plan Review Notes For Permit 02111908
Permit Number 02111908
Review Stop B
Sequence Number 1
Notes
Date Text
2003-01-07 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02111908
 ADD: 1805 OKEECHOBEE ROAD
 CONT:GLOBAL CONSTRUCTION
 TEL: (954)971-9500
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE CORRECT ADDRESS FOR THIS BUILDING
 IS 1805 OKEECHOBEE ROAD, THERE IS NO
 OLD OKEECHOBEE RD IN THE CITY, THIS IS
 NAME OF THE SAME ROAD LOCATED IN THE
 COUNTY. IF GIVEN THIS TO 911 RESPONCE
 THEY MAY RESPOND IN THE COUNTY!
  
 2) 105.3 ADMINISTRATIVE CODE- RESIDENT
 INSPECTOR PROGRAM REQUIRED. (5) FOR
 BUILDINGS GREATER THAN 20,000 SQ FT.
 CONTACT DON NEELY DIRECTOR OF RESIDENT
 INSPECTOR PROGRAM.
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORD, 3 DOCUMENTS WILL BE REQUIRED.
 PLANS, ENGINEERING REPORTS, PRODUCT
 APPROVALS, SHOP DRAWINGS OR SUBMITTALS,
 ETC...
  
 3) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
  
 5) SITE STATISTICS: COMMENT: 503.4 VS
 TABLE 600. 503.4 UNLIMITED AREA WHEN AN
 AUTOMATIC EXTINGUISHING SYSTEM IS USED
 & ACCOMPANIED BY 60' OPEN SPACE AROUND
 BUILDING, THIS BUILDING DOESN'T QUALIFY
 UNDER THE 60' OPEN SPACE. THE BUILDING
 FRONTAGE CAN ONLY BE TAKEN TO THE CENTER
 LINE OF THE ROAD!
 TABLE 500 FOR A TYPE IV BLDG. 1HR.
 PRO. FULLY SPRINKLERED DOES QUALIFY THE
 BLDG TO :
 A) FACTORY/ INDUSTRIAL94,500 SQ FT
 B) STORAGE 72,000 W/ AREA INCREASES
 100% UNSPR AREA= 96,000 SQ FT.
  
 THE PLANS HAVE NO INFORMATION FOR THE
 FIRE SPRINKLER SYSTEM, IS THERE GOING TO
 BE ONE? PLEASE PROVIDE ADD INFORMATION.
 FIRE SPRINKLER PLANS TO BE ENGINEERED,
 SIGNED,SEALED & DATED. 3 SETS PRIOR TO
 ISSUANCE OF THIS PERMIT. 903.1.
  
 6)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
 PLANS INDICATE MULTIPLE TENANTS SUCH
 AS 1873, 1877, 1889 & 1893 WITHOUT
 ACCESSIBLE ENTRANCES?
  
 7) 1007.5.5 HANDRAILS SHALL EXTEND @
 LEAST 12" HORIZONTALLY BEYOND THE TOP
 RISER OF A FLIGHT OF STAIRS. SEE A-10,
 DETAIL 3.
  
 8) SHEET A-9 DETAIL 2 CURRENTLY MEETS
 CODE SINCE IT IS NOT A REQUIRED MEANS OF
 EGRESS. IF AT TENANT FIT UP THIS IS THE
 ONLY MEANS OF EGRESS THEN THE EXCEPTION
 #1 WILL NOT COMPLY.
  
 9) PLEASE PROVIDE DETAILS FOR 1 HR RAT-
 ING FOR BEAMS, GIRDERS, ROOF FRAMING
 (BAR JOIST) TABLE 600- 1 HR PROTECTED.
  
 10) FIRE DISTRICT 102.2.4 ROOF COVERINGS
 MUST BE A "A OR B" ROOF COVERING SUMIT
 MANUFACTURES SPEC.
  
 11)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 12)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) SWING DOORS, GLAZED, SOLID & LOUVERS
 B) OVERHEAD GARAGE DOORS
 C) WINDOWS
 D) VERTICAL & HORIZONTAL MULLIONS
 E) ROOFING ASSEMBLIES
 F) SKYLIGHTS
  
 13)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 13) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 14) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 15)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 16)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 17) 103.6 COUNTY ADMINISTRATIVE CODE:
 1606.1.4 & 1707.1.4, CITY STANDARD(13)
 IN ORDER TO ASSURE THE SECURING OF SHUT-
 TERS ON LARGE BUILDINGS, A PRE-STORM
 PREPARATION PLANS MUST BE SUBMITTED BY
 THE PROPERTY OWNER OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES
 DEPARTMENT. ANY SUCH PLAN SHALL INCLUDE
 AT A MINIMUM, ON SITE LOCATION FOR
 STORM SHUTTERS, PARTY RESPONSIBLE FOR
 THE SECURING THE SHUTTERS (SAID PARTIES
 MUST BE LOCATED IN PALM BEACH COUNTY),
 TOTAL NUMBER OF OPENINGS TO BE PROTECTED
 AND THE TOTAL TIME REQUIRED TO SECURE
 ALL OPENINGS. PROTECTION OF OPENINGS
 SHALL BE ACCOMPLISHED WITHIN 12 HRS.
 OR LESS OF THE OFFICIAL NOTIFICATION BY
 THE NATIONAL WEATHER SERVICE OF A
 HURRICANE WATCH.
  
 18) 1504.1 ROOFING: INSULATION/ FASTEN-
 ING SCHEDULE WILL REQUIRE WINDLOADS/
 WIND REISTANCE TESTING FOR WIND ZONE.
  
 19) STRUCTURAL STEEL SHOP DRAWINGS ARE
 TO BE REVIEWED BY THE ENGINEER OF RECORD
 BEFORE THE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
  
 20) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 21)2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM C-1063.
  
 22)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026