2003-05-06 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 02111907 |
| ADD:1701 OKEECHOBEE RD STE 1743 |
| CONT:GLOBAL CONSTRUCTION |
| CONTACT : GARY TALTON |
| TEL: (561)351-4134 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| *****BUILDING PROVISO******* |
| 1) THE AREA ABOVE "THE AREA OF REFUGE" |
| SIGN INDICATING "NOT TO BE USED AS A |
| STORAGE AREA"!!!! NOT INTENDED FOR THAT |
| USE, THE MINIMUM LOADING WOULD HAVE TO |
| BE 125 LBS. |
| ******OR******* |
| IF THIS AREA IS ENTENDED FOR STORAGE: |
| 106.4.2 STORAGE & FACTORY- INDUS- |
| TRIAL OCCUPANCIES. IT SHALL BE THE |
| RESPONSIBILITY OF THE OWNER, AGENT, |
| PROPIETOR OR OCCUPANT OF GROUP S AND |
| GROUP F OCCUPANCIES, OR ANY OCCUPANCY |
| WHERE EXCESSIVE FLOOR LOADING IS LIKELY |
| TO OCCUR, TO EMPLOY A COMPETENT ARCHI- |
| TECT OR ENGINEER IN COMPUTING THE SAFE |
| FLOOR LOAD CAPACITY. ALL SUCH COMPUTA- |
| TIONS SHALL BE ACCOMPANIED BY AN AFFA- |
| DAVIT FROM THE ARCHITECT OR ENGINEER |
| STATING THE SAFE ALLOWABLE FLOOR LOADS |
| ON EACH FLOOR IN POUNDS PER SQ FT.THE |
| COMPUTATIONS & AFFADAVIT SHALL BE FILED |
| AS A PERMANENT RECORD OF THE BLDG DEPT. |
| |
| 106.4.3.SIGNS REQUIRED. IN EVERY |
| BUILDING OR PART OF A BUILDING USED FOR |
| STORAGE, INDUSTRIAL OR HAZARDOUS PUR- |
| POSES, THE SAFE FLOOR LOADS, AS REVIEWED |
| BY THE BUILDING OFFICIAL ON THE PLAN, |
| SHALL BE MARKED ON PLATES OF APPROVED DE |
| SIGN WHICH SHALL BE SUPPLIED & SECURELY |
| AFFIXED BY THE OWNER OF THE BUILDING IN |
| A CONSPICUOUS PLACE IN EACH STORY TO |
| WHICH THEY RELATE. SUCH PLATES SHALL NOT |
| BE REMOVEDOR DEFACED, & IF LOST, |
| REMOVED THE OWNER OF THE BUILDING SHALL |
| REPLACE THEM. |
| |
| JIM WITMER |
| BUILDING PLAN REVIEW |