Plan Review Notes For Permit 02111907 |
Permit Number |
02111907 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-04-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SHT 1.0 KITCHEN SINK SHALL COMPLY | | WITH 11-4.24 AND ALL SUBSECTIONS. PLEASE | | PROVIDE DETAILS. | | 2) SHT 3.1 CLEANOUTS SHALL BE INSTALLED | | AT EACH CHANGE OF DIRECTION OF THE BLDG | | DRAIN OR HORIZONTAL WASTE OR SOIL LINES | | GREATER THAN 45 DEGREES. SEC. 708.3.3 | | 3) SHT 3.1 A SECOND DRINKING FOUNTAIN IS | | REQUIRED PER TABLE 403.1. THE HIGH/LOW | | IS CONSIDERED A SINGLE FIXTURE. ALSO SEE | | SECTION 410.1 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|