Plan Review Notes For Permit 02111907 |
Permit Number |
02111907 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-27 00:00:00 | DENIED: | | | | PLAN SHEET 3.2 INDICATES OUTSIDE AIR | | CALCULATION (#4) 2437 SQ FT @ .3 CFM PER | | FT.IS THIS CALCULATION FOR THE SPACE | | MARKED 130 OR 129 ON SHEET 1.0?PLEASE | | PROVIDE OUTSIDE AIR CALCULATIONS FOR ALL | | AREAS. | | | | EXHAUST FAN #2 IS NOT LISTED ON THE | | FAN SCHEDULE.PLEASE IDENTIFY. | | | | PROVIDE INFORMATION ON THE CONDENSATE. | | INDICATE TERMINATION LOCATIONS.UNITS | | LARGER THAN 6 TONS SHALL DICHARGE TO | | STORM DRAIN OR DRY WELL. | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | SHALL HAVE: | | ACTIVATION OF ANY AIR DISTRIBUTION | | SYSTEM SMOKE DETECTOR CAUSES A | | SUPERVISORY SIGNAL TO BE INDICATED AT | | A CONSTANTLY ATTENDED LOCATION OR SHALL | | HAVE AN ALARM/STROBE IN NORMALLY | | OCCUPIED AREA.NFPA 90A 4-4.4.2 OR | | 4-4.4.3 (A). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|