2002-12-27 00:00:00DENIED:
  
 PLAN SHEET 3.2 INDICATES OUTSIDE AIR
 CALCULATION (#4) 2437 SQ FT @ .3 CFM PER
 FT.IS THIS CALCULATION FOR THE SPACE
 MARKED 130 OR 129 ON SHEET 1.0?PLEASE
 PROVIDE OUTSIDE AIR CALCULATIONS FOR ALL
 AREAS.
  
 EXHAUST FAN #2 IS NOT LISTED ON THE
 FAN SCHEDULE.PLEASE IDENTIFY.
  
 PROVIDE INFORMATION ON THE CONDENSATE.
 INDICATE TERMINATION LOCATIONS.UNITS
 LARGER THAN 6 TONS SHALL DICHARGE TO
 STORM DRAIN OR DRY WELL.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE:
 ACTIVATION OF ANY AIR DISTRIBUTION
 SYSTEM SMOKE DETECTOR CAUSES A
 SUPERVISORY SIGNAL TO BE INDICATED AT
 A CONSTANTLY ATTENDED LOCATION OR SHALL
 HAVE AN ALARM/STROBE IN NORMALLY
 OCCUPIED AREA.NFPA 90A 4-4.4.2 OR
 4-4.4.3 (A).
  