Plan Review Notes For Permit 02111907 |
Permit Number |
02111907 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-12 00:00:00 | 1) IT APPEARS THAT SOME EXIT ACCESS | | OCCURS WITHIN SPACE 130 FROM THE | | OFFICES. IS IT NOT TRUE THAT SPACE 130 | | CAN BE CONSIDERED MORE HAZARDOUS THAN | | THE OFFICE AREA. PLEASE SEE NFPA 101, | | THE LIFE SAFETY CODE, 2000 EDITION, | | SECTION 7.5.2.1, IMPEDIMENTS TO EXITS. | | | | 2) SEPARATE PLANS AND PERMITS | | REQUIRED FOR THE PLANNED REMODEL OF | | THE FIRE ALARM SYSTEM. | | | | 3) NO FIRE SPRINKLER SYSTEM DRAWINGS | | AS NOTED ON TITLE PAGE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|