Plan Review Notes
Plan Review Notes For Permit 02111907
Permit Number 02111907
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-05 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY DIRECTION OF
 PANELS. PANELS SEEM TO BE FACING RM
 112 AND NOT IN THE SAME LOCATION OF
 TRANSFORMER?
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN PANEL "H1"
 TRANSFORMER AND PANELS "L1 AND "L".
 250-122/250-24/250-30
 PLEASE ALSO SHOW EQUIPMENT GROUNDING
 MEANS BETWEEN
  
 3)NOTE: PLEASE CLARIFY/ NEW OR EXSITNG
 SHOW WINDOW RECEPTS PER 210-62
  
 4)NOTE: PLEASE CLARIFY CIRCUITING FOR
 EM LT/ EXT LTS SHOWN PER 700-12E.
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372