2002-12-26 00:00:00**************UNSAT *************
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS
 SUBMITTED, LOAD IS SHOWN AT 223A W/ A
 200A METERCAN ENCLOSURE??
 PLEASE ALSO NOTE, LOAD CALCS STILL DO
 NOT INCLUDE HEAT PUMP IN LOAD AND
 SIZING OF UNIT.
 SPECS ARE SUBMITTED FOR HEAT PUMP SHOW-
 -ING 6 DIFFERENT SIZES????
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  