Plan Review Notes
Plan Review Notes For Permit 02111609
Permit Number 02111609
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-11 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 WITH NEW HEAT PUMP LOAD BEING ADDED AND
 SHOW ALL EXISTING LOADS ALSO.
 PLEASE SHOW SIZE OF EXIST. SERVICE.
 215-5
  
 2)NOTE: PLEASE SEE RISER DIAGRAM FOR
 WIRING OF HEATER. PLEASE NOTE SUBMITTAL
 SHOW NEW HEAT PUMP MIN CIRCUIT AMPACITY
 AT 40AMPS, AND RISER SHOWS #12'S?
 PLEASE SEE 310-16 FOR RATING OF WIRE.
 AND OCP.
  
 3)NOTE: PLEASE SEE 250-122 FOR SIZING
 EQUIPMENT GROUND TO HEATER. SHOWN AS #12
 ALSO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372