2003-01-21 00:00:00 | BUILDING DENIED |
| |
| 1) SHEETS A1 AND A2 DO NOT HAVE THE |
| EMBOSSED SEAL OF ARCHITECT THAT SIGNED |
| THE PLANS. |
| |
| 2) A1 OF PLANS INDICATE PLYWOOD WILL BE |
| USED AS THE OPENING PROTECTION FOR THE |
| FRENCH DOOR. THIS IS ALLOWED WHERE |
| WIND SPEEDS DO NOT EXCEED 130 MPH, |
| HOWEVER THE WIND SPEED FOR THE CITY OF |
| WPB IS 140 MPH. PLEASE SUBMIT PRODUCT |
| APPROVALS FOR STORM PANELS. FBC 1606.1.4 |
| |
| 3)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - NEW EXTERIOR DOORS |
| - STORM PANELS |
| |
| 4) PROVIDE ENERGY CALCULATIONS AS |
| REQIRED BY FBC CHAPTER 13. |
| |
| 5) DETAIL #3 ON A1 SPECIFIES A MINIMUM |
| OF R12 INSULATION IN THE ATTIC. THE FBC |
| CHAPTER 13 SECTION 604.1 REQUIRES |
| CEILINGS TO HAVE AN INSULATION LEVEL OF |
| AT LEAST R-19. |
| |
| 6) SPECIFY THE SIZE AND SPACING OF THE |
| TAPCONS INDICATED IN DETAIL #7 ON A1. |
| PLEASE CLARIFY IF THE BRICK VENEER THAT |
| THE NEW WALLS ARE BEING ATTACHED TO IS |
| A STRUCTURAL ELEMENT. |
| |
| 7) PROVIDE THE UL LISTING INFORMATION |
| AND MANUFACTURER'S SPECS. FOR THE PRE- |
| FABRICATED FLUE PIPE. FBC 2804.4. |
| |
| 8) AN EXTERIOR DOOR FROM THE CLOSET TO |
| THE DECK IS SHOWN ON THE FLOOR PLAN AND |
| THE HVAC/ELEC PLAN ON A1, BUT NOT ON THE |
| EAST ELEVATION ON SHEET A2. PLAESE |
| CLARIFY. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |