Plan Review Notes
Plan Review Notes For Permit 02111254
Permit Number 02111254
Review Stop B
Sequence Number 1
Notes
Date Text
2002-12-19 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3) PROVIDE ELEVATION, FLOOR PLAN,
 FOUNDATION PLAN AND WALL SECTION OF THE
 EXISTING STRUCTURE OF THE AREA WHERE THE
 ADDITION IS TO BE CONSTRUCTED.
  
 4) INDICATE ON THE PLANS HOW THE ROOMS
 ADJACENT TO THE ADDITION WILL COMPLY
 WITH EMERGENCY EGRESS REQUIREMENTS. SEE
 FBC 1005.4.
  
 5) INDICATE ON THE PLANS THE GUARDRAIL
 HEIGHT AND THE SPACING BETWEEN THE
 INTERMEDIATE RAILS.SEE FBC 1015 & 1026.5
  
 6) PROVIDE A FLOOR FRAMING PLAN FOR THE
 ADDITION. SPECIFY THE JOIST SIZE,
 SPACING, ETC.
  
 7) SPECIFY ALL STRAPS, CONNECTORS,
 ANCHORS, ETC. THAT WILL BE USED TO
 PROVIDE A CONTINOUS LOAD PATH FROM THE
 ROOF TRUSSES TO THE FOUNDATION.
  
 8) NUMBER 3 ON A1 INDICATES 2X6 METAL
 STUDS AND #6 SPECIFIES 2X6 WOOD STUDS.
 PLEASE CLARIFY. IF USING METAL STUDS,
 SPECIFY THE GUAGE.
  
 9) SPECIFY THE ROOF SHEATHING NAILING
 REQUIREMENTS AS REQUIRED BY THE CITY OF
 WPB AMENDMENTS TO THE FBC TABLE 2306.1.
  
 10) REVIEW FOR SHEAR WALL REQUIREMENTS.
 SPECIFY HOW SHEAR WALL REQUIREMENTS WILL
 BE ACCOMPLISHED. SEE FBC 2308.2 FOR
 EXTERIOR WALL BRACING REQUIREMENTS
 USING STRUCTURAL WALL PANELS.
  
 11) SPECIFY ALL CONNECTORS THAT WILL BE
 USED TO RESIST UPLIFT AND OVERTURNING
 LOAD. (HOLDDOWNS,STRAPS,ETC.)
  
 12) CHECK FOR HORIZONTAL DIAPHRAM
 REQUIREMENTS. SPECIFY HOW THIS WILL BE
 ACCOMPLISHED. SEE FBC 2310.
  
 13)FL BLD CODE 2309.6 ATTIC ACCESS,
 INDICATE OPENING SIZE.
  
 14) SPECIFY ATTIC VENTILATION PER FBC
 2309.7.
  
 15) SPECIFY BRACING FOR GABLE END PER
 FBC 2313.4.
  
 16) SPECIFY THE CONNECTION BETWEEN THE
 NEW WALLS AND THE EXISTING STRUCTURE.
 INDICATE THE TYPE OF CONSTRUCTION OF THE
 EXISTING STRUCTURE. FBC 104.1.5
  
 17) PROVIDE STRUCTURAL DETAILS FOR THE
 CONSTRUCTION OF THE CHIMNEY EXTENSION.
 FBC 104.1.5
  
 18) PROVIDE LISTING INFORMATION AND
 MANUFACTURER'S SPECIFICATIONS FOR THE
 PREFAB CHIMNEY PIPE. FBC 2804.4
  
 19) INDICATE THE ROOF PITCH, MEAN ROOF
 HEIGHT, WALL HEIGHTS, ETC. FBC 104.1.5
  
 20)FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
 OWNER/AGENT IS REQUIRED TO SIGN AND DATE
 FORM.
  
 21) SPECIFY CEILING INSULATION AS
 REQUIRED BY FBC CHAPTER 13.
  
 22) SPECIFY ON THE DECK EXTENSION DETAIL
 ON A2 IF POST IS EMBEDDED IN CONCRETE.
 INDICATE HOW UPLIFT AND GRAVITY LOADS
 ARE BEING RESISTED. INDICATE THE TYPE OF
 PRESERVATIVE TREATMENT. SEE FBC 1805,
 1811 AND 1606.
  
 22) PROVIDE DOOR BUCK DETAILS. SEE FBC
 1707.4.4.
  
 23) SPECIFY THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURE (PSF) AT NEW DOOR
 OPENING. FBC 1606.1.7
  
 24) INDICATE OPENING PROTECTION FOR
 GLAZING IN FRENCH DOOR. FBC 1606.1.4
  
 25) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRENCH DOOR
 - STORM PANELS
  
 26) THE ARCHITECT IS REQUIRED TO SIGN
 AND DATE THE DRAWINGS, IN ADDITION TO
 EMBOSSING THEM. A SIGNATURE STAMP IS NOT
 ACCEPTABLE. SEE FAC 61G
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW