2003-01-23 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-ROOF ZONE #3 DOESN'T APPLY GABLE ENDS |
| ONLY. IT APPLIES TO CORNERS AS WELL |
| FOR FASTENER TYPE AND SPACING. SEE |
| SEC. 2306.1 CITY AMENDMENTS TO FBC/01. |
| 2-SUPPORTS FOR WWM IN CONCRETE SLAB TO |
| COMPLY WITH SECTION 1909.3 FBC 2001. |
| 3-PROVIDE COMPLETE FRAMING DETAIL FOR |
| ARCHED OPENINGS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 4-PROVIDE COMPLETE SECTION/DETAIL FOR |
| CONSTRUCTION OF KNEE WALL AT ENTRY. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 5-SPECIFY CONNECTORS AT TOP AND BOTTOM |
| OF WOOD COLUMNS THAT RESIST THE UPLIFT |
| LOADS CALCULATED. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 6-CLARIFY ROOF FRAMING AT REAR PORCH. |
| WHERE ARE TRUSSES RESTING ON IF THERE |
| IS NOT BEAM THERE. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 7-PROVIDE UPDATED PRODUCT APPROVAL FOR |
| ROOF TILE. |
| 8-PROVIDE PRODUCT APPROVAL FOR FIXED |
| WINDOWS WITH THE SIZES SHOWN ON PLANS. |
| 9-PROVIDE UL LISTING AND SPECS FOR BBQ. |
| 10-PROVIDE PRODUCT APPROVAL FOR FRENCH |
| DOORS WITH SIDELITES AND TRANSOM ABOVE |
| SINGLE ASSEMBLY AS SHOWN ON PLANS. |
| PRODUCT APPROVAL SUBMITTED IS TO BE |
| USED WITH WINDOWS ONLY, NOT DOORS. |
| 11-PROVIDE PRODUCT APPROVAL FOR SLIDING |
| GLASS DOORS WITH TRANSOM ABOVE SINGLE |
| ASSEMBLY AS SHOWN ON PLANS. |