Plan Review Notes
Plan Review Notes For Permit 02111239
Permit Number 02111239
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-26 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE SIZE OF NAIL FOR ROOF SHEATHING
 AT ZONE 3. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001.
 2-SPECIFY CONCRETE SLAB JOINTS. SEE SEC.
 1909.3 FBC 2001.
 3-PROVIDE COMPLETE STRUCTURAL DETAIL FOR
 HANGING OF A/C UNITS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE COMPLETE FRAMING DETAIL FOR
 ARCHED OPENINGS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 5-PROVIDE COMPLETE SECTION/DETAIL FOR
 CONSTRUCTION OF KNEE WALL AT ENTRY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-CONNECTORS SPECIFIED FOR WOOD COLUMN
 AT MASTER BEDROOM DOESN'T RESIST THE
 CALCULATED UPLIFT LOADS. REVISEAS
 REQUIRED. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 7-CLARIFY ROOF FRAMING AT REAR PORCH.
 WHERE ARE TRUSSES RESTING ON IF THERE
 IS NOT BEAM SHOWN. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 8-PRODUCT APPROVAL FOR ROOF TILE IS
 EXPIRED. RESUBMIT UPDATED ONE.
 9-PROVIDE PRODUCT APPROVAL FOR FIXED
 WINDOWS WITH THE SIZES SHOWN ON PLANS.
 10-PROVIDE UL LISTING AND SPECS FOR BBQ.
 11-A)PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS WITH SIDELITES AND TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 (NOTE: PRODUCT APPROVAL IS FOR WINDOW
 ASSEMBLIES ONLY, NOT FOR DOORS)
 B)PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 (NOTE: HEAD RECEPTOR IS NOT ALLOWED ON
 PRODUCT APPROVAL SUBMITTED. SEE THE
 LIMITATIONS ON PAGE 2 OF PRODUCT APPRO
 VAL).
 12-GLASS BLOCK TO BE SAFETY GLASS IF THE
 UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEE SEC. 2405.2.2 FBC 2001.