2002-12-27 00:00:00 | CHECKLIST: |
| 1-2ND FLOOR PLAN DOESN'T MATCH EXTERIOR |
| REAR ELEVATION LOCATION OF WINDOW. |
| 2-FRAMING PLANS ARE VERY CONFUSING AND |
| MISSING STRUCTURAL DETAILS AND SPECS: |
| A)TRUSS GIRDERS DON'T SHOW ANY POST AT |
| THE ENDS. |
| B)PROVIDE COMPLETE SECTION/DETAIL AT |
| FRONT ELEVATION CONSTRUCTION SHOWING |
| ATTACHMENT OF FRAMED WALL TO GIRDER |
| TRUSS AND ATTACHMENT OF GIRDER TRUSS |
| AT THE ENDS. |
| C)CLARIFY WHY THERE ARE ONLY A COUPLE |
| OF SHEARWALLS SHOWN ON TWO SIDES ONLY. |
| WHAT ABOUT THE OTHER SIDES? |
| D)PROVIDE DETAILS AND SPECS FOR FRAMING |
| AT THE CORNERS. HOW ARE THE LOADS |
| TRANSFERRED AT CORNERS? |
| E)FOUNDATION PLAN DON'T MATCH BEARING |
| WALLS SHOWN ON FIRST FLOOR PLAN. |
| F)2ND FLOOR FRAMING PLAN IS MISSING |
| SPECS FOR SOME HEADERS. |
| G)REVISE/UPDATE ANCHOR SCHEDULE. SEE USP |
| CATALOGUE FOR PROPER CONNECTOR AND |
| ENGINEERED VALUES. PROVIDE ENGINEERING |
| CALCULATIONS FOR VALUES THAT ARE |
| DIFFERENT FROM THOSE PUBLISHED IN THE |
| USP CATALOGUE. |
| H)SOME CONNECTORS SPECIFIED ON ROOF |
| FRAMING PLANS DON'T RESIST CALCULATED |
| LOADS SHOWN ON PLANS. REVISE AS REQ'D. |
| SECTION 104.2.1.2 CITY AMENDMENTS TO |
| FBC 2001. |
| |
| 3-SPECIFY CONTROL JOINTS IN CONCRETE |
| SLAB OR CLEARLY SPECIFY SUPPORTS FOR |
| WWM. SEE SEC. 1909.3 FBC 2001. |
| 4-SPECIFY SAFETY GLASS AT BATH #2 AND |
| AT FAMILY AREA. SEE PLANS AND SECTION |
| 2405.2 FBC 2001. |
| 5-PROVIDE COMPLETE STRUCTURAL DETAIL FOR |
| INSTALLATION OF STEEL PIPE AT GARAGE |
| FOR PROTECTION OF WATER HEATER. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 6-PROVIDE ATTIC ACCESS ABOVE GARAGE, |
| MAIN ROOF AND 2ND FLOOR. |
| SEC. 2309.6 FBC 2001. |
| 7-PROVIDE SMOKE DETECTOR AT 1ST FLOOR BY |
| THE STAIRS. SEC. 905.2.2 FBC 2001. |
| 8-SITE SPECIFIC STORM SHUTTERS INSTALLA- |
| TION WILL REQUIRE A CERTIFICATE OF |
| COMPLIANCE AND INSTALLATION AFFIDAVIT |
| AS REQUIRED BY THE CITY IMPLEMENTATION |
| STANDARD FOR HURRICANE MISSILE IMPACT |
| PROTECTION (ITEMS 15, 16 AND 17). |
| 9-NEED PRODUCT APPROVAL FOR: |
| A)ROOF CONCRETE TILE: ONE SUBMITTED IS |
| EXPIRED. |
| B)GARAGE DOORS: PRODUCT APPROVAL WAS |
| DELETED FROM SBCCI. NEED A NEW ONE. |
| |
| 10-REVISE ENERGY CALCULATIONS: UNDER THE |
| ATTIC AREA IS INCORRECT. SEE SECTION |
| 604.1.A.1 OF CHAPTER 13 OF FBC 2001. |
| 11-OWES $236.27 FOR UPDATED VALUE AND |
| RADON FEES. |
| |
| NOTE: |
| PLEASE RETURN REVIEWED SET AFTER CORREC- |
| TIONS ARE MADE TO THE ORIGINAL CAD DWGS |
| IN ORDER TO EXPEDITE THE REVIEW PROCESS. |
| IN THE PAST CORRECTIONS WERE DONE ON THE |
| BLUEPRINTS. DOES WHY MOST OF THE |
| COMMENTS WERE ADDRESSED ON PREVIEWS PLAN |
| REVIEWS BUT THEY WERE NOT REVISED ON THE |
| ORIGINAL CAD DRAWINGS. |