Plan Review Notes
Plan Review Notes For Permit 02111218
Permit Number 02111218
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-27 00:00:00CHECKLIST:
 1-2ND FLOOR PLAN DOESN'T MATCH EXTERIOR
 REAR ELEVATION LOCATION OF WINDOW.
 2-FRAMING PLANS ARE VERY CONFUSING AND
 MISSING STRUCTURAL DETAILS AND SPECS:
 A)TRUSS GIRDERS DON'T SHOW ANY POST AT
 THE ENDS.
 B)PROVIDE COMPLETE SECTION/DETAIL AT
 FRONT ELEVATION CONSTRUCTION SHOWING
 ATTACHMENT OF FRAMED WALL TO GIRDER
 TRUSS AND ATTACHMENT OF GIRDER TRUSS
 AT THE ENDS.
 C)CLARIFY WHY THERE ARE ONLY A COUPLE
 OF SHEARWALLS SHOWN ON TWO SIDES ONLY.
 WHAT ABOUT THE OTHER SIDES?
 D)PROVIDE DETAILS AND SPECS FOR FRAMING
 AT THE CORNERS. HOW ARE THE LOADS
 TRANSFERRED AT CORNERS?
 E)FOUNDATION PLAN DON'T MATCH BEARING
 WALLS SHOWN ON FIRST FLOOR PLAN.
 F)2ND FLOOR FRAMING PLAN IS MISSING
 SPECS FOR SOME HEADERS.
 G)REVISE/UPDATE ANCHOR SCHEDULE. SEE USP
 CATALOGUE FOR PROPER CONNECTOR AND
 ENGINEERED VALUES. PROVIDE ENGINEERING
 CALCULATIONS FOR VALUES THAT ARE
 DIFFERENT FROM THOSE PUBLISHED IN THE
 USP CATALOGUE.
 H)SOME CONNECTORS SPECIFIED ON ROOF
 FRAMING PLANS DON'T RESIST CALCULATED
 LOADS SHOWN ON PLANS. REVISE AS REQ'D.
 SECTION 104.2.1.2 CITY AMENDMENTS TO
 FBC 2001.
  
 3-SPECIFY CONTROL JOINTS IN CONCRETE
 SLAB OR CLEARLY SPECIFY SUPPORTS FOR
 WWM. SEE SEC. 1909.3 FBC 2001.
 4-SPECIFY SAFETY GLASS AT BATH #2 AND
 AT FAMILY AREA. SEE PLANS AND SECTION
 2405.2 FBC 2001.
 5-PROVIDE COMPLETE STRUCTURAL DETAIL FOR
 INSTALLATION OF STEEL PIPE AT GARAGE
 FOR PROTECTION OF WATER HEATER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-PROVIDE ATTIC ACCESS ABOVE GARAGE,
 MAIN ROOF AND 2ND FLOOR.
 SEC. 2309.6 FBC 2001.
 7-PROVIDE SMOKE DETECTOR AT 1ST FLOOR BY
 THE STAIRS. SEC. 905.2.2 FBC 2001.
 8-SITE SPECIFIC STORM SHUTTERS INSTALLA-
 TION WILL REQUIRE A CERTIFICATE OF
 COMPLIANCE AND INSTALLATION AFFIDAVIT
 AS REQUIRED BY THE CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION (ITEMS 15, 16 AND 17).
 9-NEED PRODUCT APPROVAL FOR:
 A)ROOF CONCRETE TILE: ONE SUBMITTED IS
 EXPIRED.
 B)GARAGE DOORS: PRODUCT APPROVAL WAS
 DELETED FROM SBCCI. NEED A NEW ONE.
  
 10-REVISE ENERGY CALCULATIONS: UNDER THE
 ATTIC AREA IS INCORRECT. SEE SECTION
 604.1.A.1 OF CHAPTER 13 OF FBC 2001.
 11-OWES $236.27 FOR UPDATED VALUE AND
 RADON FEES.
  
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER CORREC-
 TIONS ARE MADE TO THE ORIGINAL CAD DWGS
 IN ORDER TO EXPEDITE THE REVIEW PROCESS.
 IN THE PAST CORRECTIONS WERE DONE ON THE
 BLUEPRINTS. DOES WHY MOST OF THE
 COMMENTS WERE ADDRESSED ON PREVIEWS PLAN
 REVIEWS BUT THEY WERE NOT REVISED ON THE
 ORIGINAL CAD DRAWINGS.