Plan Review Notes For Permit 02111045 |
Permit Number |
02111045 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-16 00:00:00 | CHECKLIST: | | 1-REVISE ENERGY CALCULATIONS: A/C AREA | | DOESN'T MATCH A/C AREA SHOWN ON PLANS. | | 2-A/C AREA SHOWN ON COUNTY IMPACT FEE | | STAMP DOESN'T MATCH A/C AREA ON PLANS. | | REVISE AS REQUIRED. | | 3-PROVIDE SOIL TEST REPORT. | | 4-SPECIFY SIZE OF ANCHOR AND WASHER FOR | | GARAGE DOOR STRUCTURAL BUCK DETAIL. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC | | 2001. | | 5-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS OR APPLY FOR SEPARATE PERMIT | | AS REQUIRED BY CITY IMPLEMENTATION | | STANDARD FOR HURRICANE MISSILE IMPACT | | PROTECTION. | | 6-BUILDING SECTION A/A-5: REVISE HEIGHT | | OF HANDRAIL. SEE SECTION 1007.5.1 | | FBC 2001. |
|