2002-12-17 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8: WILL NEED THE ELEVATION
 CERTIFICATE.
 3-SPECIFY SIZE OF ANCHOR BOLT AND WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 4-CLARIFY HOW DOES THE 34SH WINDOWS
 PROVIDE THE 24" MIN. CLEAR HEIGHT.
 ALSO, DOES THE 24+5 SH WINDOW PROVIDE
 5.7 S.F. MIN. CLEAR OPENING? CLARIFY.
 SEE SEC. 1005.4.4 FBC 2001.
 5-DETAIL S21 DOESN'T WORK AT CONNECTION
 OF COLUMN P1 LOCATED BETWEEN GARAGE
 AND STAIRWAY. REVISE AS REQ'D. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-REVISE CONNECTOR TC-1 SPECIFIED ON
 ROOF FRAMING PLAN AT FRONT ELEVATION.
 NEED WOOD TO WOOD CONNECTORS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.