Plan Review Notes
Plan Review Notes For Permit 02110849
Permit Number 02110849
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-11 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. WILL NEED THE ELEVATION
 CERTIFICATE.
 3-2ND FLOOR FRAMING PLAN: SPECIFY
 DRAFSTOPPING LOCATION AT AREAS NOT TO
 EXCEED 500 S.F. AS REQUIRED BY SECTION
 2305.2.2 FBC 2001.
 4-SPECIFY SIZE OF ANCHOR BOLT AND WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SE. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-24SH AND 34SH WINDOWS DON'T PROVIDE
 THE 24" MIN. CLEAR HEIGHT OPENING AS
 REQUIRED BY SEC. 105.4.4 FBC 2001.
 ALSO, 24SH WINDOWS DON'T PROVIDE THE
 5.7 S.F. MIN. CLEAR OPENING. REVISE
 CLARIFY AS REQUIRED.
 6-DETAIL S21 DOESN'T WORK FOR WOOD COL.
 P1 LOCATED BET. GARAGE & STAIRWAY.
 REVISE/ CLARIFY AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-REVISE CONNECTOR TC-1 ON ROOF FRAMING
 PLAN AT FRONT ELEVATION. TC CONNECTORS
 ARE FOR WOOD TO CONCRETE. NEED WOOD TO
 WOOD CONNECTORS AT FRAMED WALL. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.