2003-02-21 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE COMMENTS FROM FIRST
 REVIEW, AIC RATING IS NOW SHOWN FOR
 TYPICAL PANEL, BUT NOT FOR MAIN DISC`S.
 PLEASE SHOW.
  
 2)NOTE: IT WAS NOTED ON PLAN FOR CIRCUIT
 -ING TO MEET 700-12E FOR EM/EXT LTS,BUT
 CIRCUITS ARE STILL LABELED AS SEPARATE.?
  
 3)NOTE: PLEASE SHOW EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN DSIC`S AND PANELS
 SIZE PER 250-122
  
 4)NOTE: PLEASE CLARIFY VOLTAGE SHOWN
 AS 150/208, SHOULD BE 120/208
  
 5)NOTE: PLEASE SHOW A "PANEL" SCHEDULE.
 SHOWN NOW W/ 2500 W ON 15A BRKR AND #14
 AWG.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW