Plan Review Notes For Permit 02110845 |
Permit Number |
02110845 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-02-21 00:00:00 | *********** UNSAT **************** | | | | 1)NOTE: PLEASE SEE COMMENTS FROM FIRST | | REVIEW, AIC RATING IS NOW SHOWN FOR | | TYPICAL PANEL, BUT NOT FOR MAIN DISC`S. | | PLEASE SHOW. | | | | 2)NOTE: IT WAS NOTED ON PLAN FOR CIRCUIT | | -ING TO MEET 700-12E FOR EM/EXT LTS,BUT | | CIRCUITS ARE STILL LABELED AS SEPARATE.? | | | | 3)NOTE: PLEASE SHOW EQUIPMENT GROUNDING | | CONDUCTOR BETWEEN MAIN DSIC`S AND PANELS | | SIZE PER 250-122 | | | | 4)NOTE: PLEASE CLARIFY VOLTAGE SHOWN | | AS 150/208, SHOULD BE 120/208 | | | | 5)NOTE: PLEASE SHOW A "PANEL" SCHEDULE. | | SHOWN NOW W/ 2500 W ON 15A BRKR AND #14 | | AWG. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|