Plan Review Notes
Plan Review Notes For Permit 02110845
Permit Number 02110845
Review Stop ENG
Sequence Number 1
Notes
Date Text
2002-11-22 00:00:00FAILED:
 1. INADEQUATE INFORMATIONS FOR CIVIL
 ENGINEERING REVIEW;
 A. PLEASE PROVIDE STORM WATER CALC.
 FOR OUR REVIEW AND APROVAL.
 B. DETAILS FOR THE PROPOSED EXFILTRATION
 MUST BE PROVIDED.
 C. PLEASE SHOW DETAILS, TYPE FOR THE
 CATCH BASINS.
 D. PLEASE SHOW HOW THE EXISTING LOT AS
 SHOWN IS BEING ACCSESSED.
 E. ALL DRIVEWAYS MUST BE CONSTRUCTED PER
 CITY OF WPB REQUIREMENTS AND STANDARD.
 F. DUMSTER ENCLOUSRE MUST BE CONSTRUCTED
 PER CITY OF WPB, IF TO BE PICKED UP BY
 THE CITY.
 G. POLLUTION PREVENTION PLAN MUST BE
 PROVIDED, NOTE TO THE CONTRACTOR.
 H. A RPZA BACKFLOW PREVENTER WILL NEED
 TO BE INSTALLED, IF NOT ALREADY IN PLACE
 ,AT THE WATER METER ON PRIVATE PROPERTY.
 ALL BACKFLOW PREVENTERS MUST COMPLETLY
 HIDDEN FOM VIEW WITH SHRUBS PRIOR TO
 ACTIVATION.SHOW THE LOCATION IF THERE
 IS ONE.
 I. A CLEAN OUT WILL NEED TO BE INSTALLED
 IN SANITARY SEWER LATERAL, ON THE
 PROPERTY, AT BACK OF THE SIDEWALKS, IF
 NOT ALREADY INTALLED. PLEASE SHOW THE
 LOCATIONS AND CONNECTION TO ALL THE CITY
 SERVICES.
 J. ALL OFF STREET PARKING STALLS MUST BE
 PAINTED WITH DOUBLE 4" WIDE PAINT.
 K. CITY STANDARDS MAY BE OBTAINED FROM
 PUBLIC UTILITIES ENGINEERING SERVICES
 DEPARTMENT, MR. MANNY GONZALEZ, 659-8040
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI