Plan Review Notes
Plan Review Notes For Permit 02110845
Permit Number 02110845
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-25 00:00:00**************** UNSSAT **************
  
 1)NOTE: PLEASE NOTE CIRCUITING FOR
 EM/EXIT LT NEED TO MEET 70012E
  
 2)NOTE:PLEASE SUBMIT AIC RATING FOR ALL
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 PLEASE NOTE, MAINS/PANELS/BRKRS ARE TO
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9/ 215-5.
  
 3)NOTE:PLEASE NOTE ALL HAND DRAWN CHANGE
 -S ON PLANS MUST BE RE-PRINTED OR EACH
 CHANGE MUST BE SIGNED AND DATED BY THE
 ENGINEER OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW