Plan Review Notes
Plan Review Notes For Permit 02110845
Permit Number 02110845
Review Stop B
Sequence Number 1
Notes
Date Text
2002-12-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02110845
 ADD: 1640 CLARE AVE
 CONT: MURPHY
 TEL: (561)655-3634
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTES:
 1) BLDG LOCATION IS LOCATED IN A FIRE
 ZONE.
 2) BLDG LOCATION IS IN A A9 FLOOD ZONE,
 THE BASE FINISH FLOOR ELEVATION SHALL
 BE 13.5' BY CITY ORDINANCE.
  
 COMMENTS:
 1) DISCREPANCY BETWEEN THE SURVEY AND
 SITE PLAN WITH THE SITE PLAN. THE DIMEN-
 SION OF 113' ARE REVERSED ON THE SITE
 PLAN MAKING THE CURB CUTS ONTO THE
 RIGHT OF WAY FOR THE SEABOARD RAILWAY.
  
 2) 3201.1 BUILDING IN THE RIGHT OF WAY.
 THE DIMENSION OF 108' PLUS THE 5'-0"
 SET BACK WILL MAKE THE REAR OF THE BUILD
 ING (FOUNDATION) BE PAST THE PROPERTY
 LINE.
  
 3) TABLE 600 TYPE V BUILD. REQUIRES A
 3HR WALL, @ PROPERTY LINE, WHAT TYPE OF
 AGGREGATE SHALL BE USED?SEE TABLE709.3.1
  
 4) 704.5.2 PARAPET WALLS TYPE V CONSTRUC
 TION EXTERIOR WALLS SHALL EXTEND NOT
 LESS THAN 18" ABOVE THE ROOF. SEE A-2
  
 5) GENERAL NOTES (1) BUILDING CODE IN
 AFFECT IS THE 2001 FLORIDA BUILDING CODE
 CORRECT.
  
 6)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 7)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 8) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) SWING DOORS
 B) GARAGE DOORS
 C) ROOFING ASSEMBLIES ROOFING & INSULA-
 INSULATION.
  
 9) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 10)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE SOILS REPORT, MINMIMUM BEARING
 VALUE, SIGNED & SEALED.
  
 11) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 12) 1203.4.2 EVERY TOLIET ROOM SHALL
 HAVE WINDOWS AS SPECIFIED FOR HABITABLE
 ROOMS PROVIDING IN NO CASE LESS THAN 3
 SQ FT OPEN SPACE, OR HAVE APPROVED EQUIV
 ALENT VENTILATION.
 MECH: TABLE 403.3 PUBLIC SPACES
 TOLIET ROOMS 50 CFM/ W. C. FOOTNOTE "B"
 MECH EXHAUST REQUIRED & RECIRCULATION
 IS PROHIBITED.
  
 13) SECTION 6/A3 INDICATES A TENANT
 SEPERATION WALL BUT THE DEPICTED DRAWING
 INDICATES A VOID SPACE ABOVE THE BEAM.
 INDICATE UL LISTING FOR THE VOID SPACE
 AND HR RATING.
  
 14) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PLANS INDICATE STRUCTURAL DRAWINGS
 BY OTHERS, PLEASE SUBMIT SIGNED/ SEALED
 PLANS AND ENGINEERING FOR THE TWIN T
 ROOFING SYSTEM.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved