2002-12-18 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS UNDER A SEPARATE PERMIT. |
| 2-FLOOD ZONE A8: WILL NEED TO PROVIDE |
| THE ELEVATION CERTIFICATE. |
| 3-SHEET A-1: REVISE NOTE #24. SEE SEC. |
| 1007.5.1 FOR HANDRAIL HEIGHT. |
| 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE |
| THICKNESS IS LESS THAN 0.25". |
| SEC. 2405.2.2 FBC 2001. |
| 5-SHEET A-4: REVISE NOTE #1. SEE SEC. |
| 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT. |
| 6-PROVIDE GENERAL SPECIFICATIONS FOR |
| FIREBLOCKING AT ALL CONCEALED SPACES. |
| SEC. 2305.1.4 FBC 2001. |
| 7-PROVIDE COMPLETE DETAIL/SECTION FOR |
| CONNECTION AT TOP OF COLUMN BETWEEN |
| GARAGE AND KITCHEN. CLARIFY HOW IS |
| COLUMN TOP CONNECTOR RECEIVING THE |
| TWO GIRDER TRUSSES. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 8-SHEET S-3: PROVIDE SPECIFICATIONS ON |
| STRUCTURAL WALL SECTIONS FOR FIRECUT |
| REQUIREMENTS. SEC. 2305.4 FBC 2001. |
| 9-DETAIL R19: PROVIDE COMPLETE DETAIL |
| SHOWING HOW IS GABLE END DESIGNED TO |
| PROVIDE CONTINUOUS LATERAL SUPPORT AS |
| REQUIRED BY SEC. 2117 FBC 2001 AND |
| SPECIFY ALL FASTENERS. |
| 10-PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS UNDER A SEPARATE PERMIT |
| 11-SPECIFY SIZE OF ANCHOR BOLT & WASHER |
| FOR GARAGE DOOR STRUCTURAL BUCK DETAIL |