Plan Review Notes
Plan Review Notes For Permit 02110801
Permit Number 02110801
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 THE PLAN AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 2} PLEASE SUBMIT RISER DIAGRAMS WITH ALL
 PANELS,DISCONNECTS AND GROUNDING
 SYSTEMS TO BE USED.
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4} SHOW LOCATIONS OF DISCONNECTS,PANELS
 AND GROUNDING MEANS AT ALL LOCATIONS ,ON
 PLANS.
  
 5} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CALCULATIONS PER 210-11(C)(1).
  
 6} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG,ON PANEL SCHEDULE
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE,PER 210-12.
  
 8} PLEASE SUBMIT LOAD CALCAULATIONS PER
 220,215-5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659/8096 EXT.8392