Date |
Text |
2002-11-18 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE PROVIDE THE FOLLOWING |
| INFORMATION,MAKE NECESSARY CHANGES TO |
| THE PLAN AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE NOTE THAT ALL PLANS |
| DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| ING A TITLE BLOCK, MUST BE SIGNED, |
| DATEDAND SEALED BY THE ARCH/ENGINEER OF |
| RECORD. PER FS/FAC 481.221 & 471.025 |
| |
| 2} PLEASE SUBMIT RISER DIAGRAMS WITH ALL |
| PANELS,DISCONNECTS AND GROUNDING |
| SYSTEMS TO BE USED. |
| |
| 3} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 4} SHOW LOCATIONS OF DISCONNECTS,PANELS |
| AND GROUNDING MEANS AT ALL LOCATIONS ,ON |
| PLANS. |
| |
| 5} INCLUDE SMALL APPLIANCE CIRCUITS IN |
| LOAD CALCULATIONS PER 210-11(C)(1). |
| |
| 6} PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S). PER 210-11-C-3 |
| MUST BE 20A AND #12AWG,ON PANEL SCHEDULE |
| |
| 7} PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE,PER 210-12. |
| |
| 8} PLEASE SUBMIT LOAD CALCAULATIONS PER |
| 220,215-5. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/659/8096 EXT.8392 |